Parker Hannifin 6K 사용자 설명서

다운로드
페이지 47
; IP address 172.54.125.34 
2NTCONN1 
; Attempt connection to network server #2 
2NTMPRB3,15,15,35 
; File 3, elements 15-29, in the AB PLC are mapped to  
; the 6K's binary variables VARB35-VARB49 
2NTPOLL50 
; Start polling network server #2, set interval to 50 ms 
WAIT(VARB40=b1111111100000000) 
; Wait until the value of VARB40 (mapped to file 3,  
; element 20, in the PLC) is 1111111100000000 
NTMPWB 
Network Map Binary Variables for Writing to PLC
 
Type: 
Network 
Product Rev 
Syntax: 
<!><n>NTMPWB<i>,<i>,<i>,<i> 
Units: 
n = network server # 
1
st
 i = Allen Bradley data file # 
2
nd
 i = # of the 1
st
 element in data file (beginning of range) 
3
rd
 i = # of the elements to include in range 
4
th
 i = # of the 1
st
 binary (VARB) variable in the 6K to map to 
Range: 
n = 1-6 
1
st
 i = 0-n (n depends on size of file) 
2
nd
 i = 0-n (n depends on size of file) 
3
rd
 i = 0 or 1-50 (0 disables polling for this mapping only) 
4
th
 i = 1-125 
Default: 
1NTMPWB0,0,0,0 (no mapping) 
Response: 
1NTMPWB: *1NTMPWB1,5,15,23 
See Also: 
NTCONN, NTIP, NTMPRB, NTMPWI, NTMPRI, NTPOLL, [ NTS ], TNTS, 
TNTSF, VARB 
6K 5.3 
    
<n>
 
NTMPWB
 
<i>,<i>,<i>,<i>
Network Server #
Range: 1-6
# of Allen-Bradley data file
# of first element in AB data file
      (beginning of range)
# of elements in range
# of first binary variable (VARB) in 6K
      (beginning of range, max value is 125)
EXAMPLE:
IF:
• Allen-Bradley PLC is server #2
• In the PLC’s binary data file 3, use
data elements 0-14 (15 elements
total) for binary data that is to be
transmitted from the 6K.
• Use the 6K’s binary variables 20-34
(15 variables total) to store the data
to be transmitted to the PLC.
The required mapping command is:
2NTMPWB3,0,15,20
 
The 
NTMPWB
 command maps a range of binary data elements from the AB PLC to a range of binary (
VARB
) variables in the 
6K. There are 125 
VARB
 variables available in the 6K for exchanging binary data. To perform a binary write to the PLC: 
1.  Assign the AB PLC a server number, according to its IP address (
NTIP
 command). 
2.  Connect to the AB PLC, according to its server number (
NTCONN
 command). 
3.  Map a range of binary elements in the AB PLC to a range of binary (
VARB
) variables in the 6K (
NTMPWB
 
command). 
4.  Start polling the AB device at a specific polling interval (
NTPOLL
 command). This updates binary data elements in 
the AB PLC with the data from the mapped 
VARB
 variables in the 6K.  
Saved in Non-Volatile Memory 
This command is saved in the controller’s non-volatile memory, and is remembered on power-up 
and RESET. 
Potential Error Conditions: 
•  You are not allowed to map the same 6K 
VARB
 variables for read and write functions. Nor are you allowed to map 
the same 6K 
VARB
 variables to another PLC. If you attempt either of these conditions, the 6K will not accept the 
NTMPWB
 command and will transmit the error message “
VARIABLE MAPPING CONFLICT…
”. 
•  If you attempt to write to an AB data file of the wrong type, or to a non-existent data element, the 6K will not 
accept the 
NTMPWB
 command, it will transmit the error message “
ERROR, INVALID FILE TYPE, NUMBER OR 
SIZE…
” and it will automatically stop polling all mapped binary and integer variables (equivalent to executing the 
NTMPRBi,i,0,i
NTMPWBi,i,0,i
NTMPRIi,i,0,i
, and 
NTMPWIi,i,0,i
, commands). 
page 23