Potential Error Conditions: 
•  You are not allowed to map the same 6K 
VARI
 variables for read and write functions. Nor are you allowed to map 
the same 6K 
VARI
 variables to another PLC. If you attempt either of these conditions, the 6K will not accept the 
NTMPRI
 command and will transmit the error message “
VARIABLE MAPPING CONFLICT…
”. 
•  If you attempt to read from an AB data file of the wrong type, or read from a non-existent data element, the 6K will 
not accept the 
NTMPRI
 command, it will transmit the error message “
ERROR, INVALID FILE TYPE, NUMBER 
OR SIZE…
” and it will automatically stop polling all mapped binary and integer variables (equivalent to executing 
the 
NTMPRBi,i,0,i
NTMPWBi,i,0,i
NTMPRIi,i,0,i
, and 
NTMPWIi,i,0,i
, commands). 
Control over Polling: If you want to stop the 6K from reading integer data from the PLC, but continue to exchange 
NTMPWI
NTMPRB
 and 
NTMPWB
 data, use the 
NTMPRIi,i,0,i
 command. If you need to stop polling all mapped variables, 
use the 
nNTPOLL0
 command. 
Example:   
2NTIP1,172,54,125,34 
; Identify network server #2 as an Allen-Bradley PLC at  
; IP address 172.54.125.34 
2NTCONN1 
; Attempt connection to network server #2 
2NTMPRI9,15,15,35 
; File 9, elements 15-29, in the AB PLC are mapped to  
; the 6K's integer variables VARI35-VARI49 
2NTPOLL50 
; Start polling network server #2, set interval to 50 ms 
WAIT(VARI40=22) 
; Wait until the value of VARI40 (mapped to file 9,  
; element 20, in the PLC) is 22 
 
NTMPWI 
Network Map Integer Variables for Writing to PLC
 
Type: 
Network 
Product Rev 
Syntax: 
<!><n>NTMPWI<i>,<i>,<i>,<i> 
Units: 
n = network server # 
1
st
 i = Allen Bradley data file # 
2
nd
 i = # of the 1
st
 element in data file (beginning of range) 
3
rd
 i = # of the elements to include in range 
4
th
 i = # of the 1
st
 integer (VARI) variable in the 6K to map to 
Range: 
n = 1-6 
1
st
 i = 0-n (n depends on size of file) 
2
nd
 i = 0-n (n depends on size of file) 
3
rd
 i = 0 or 1-50 (0 disables polling for this mapping only) 
4
th
 i = 1-225 
Default: 
1NTMPWI0,0,0,0 (no mapping) 
Response: 
1NTMPWI: *1NTMPWI1,5,15,23 
See Also: 
NTCONN, NTIP, NTMPRB, NTMPRI, NTMPWB, NTPOLL, [ NTS ], TNTS, 
TNTSF, VARI 
6K 5.3 
    
<n>
 
NTMPWI
 
<i>,<i>,<i>,<i>
Network Server #
Range: 1-6
# of Allen-Bradley data file
# of first element in AB data file
      (beginning of range)
# of elements in range
# of first integer variable (VARI) in 6K
      (beginning of range, max value is 225)
EXAMPLE:
IF:
• Allen-Bradley PLC is server #2
• The PLC’s integer data file 9 has 30
elements. Use data elements 0-14
(15 elements total) for integer data
to be transmitted from the 6K.
• Use the 6K’s integer variables 20-34
(15 variables total) to store the data
to be transmitted to the PLC.
The required mapping command is:
2NTMPWI9,0,15,20
 
The 
NTMPWI
 command maps a range of integer data elements from the AB PLC to a range of integer (
VARI
) variables in 
the 6K. There are 225 
VARI
 variables available in the 6K for exchanging integer data. To perform a integer write to the 
PLC: 
1.  Assign the AB PLC a server number, according to its IP address (
NTIP
 command). 
2.  Connect to the AB PLC, according to its server number (
NTCONN
 command). 
page 25