\ANO 
Network Analog Output
 
Type: 
Network 
Product Rev 
Syntax: 
<!>n\mANO.i=r 
Units: 
n = network server # 
m = module #  
i = analog output # on module “m” 
r = voltage value (VDC) 
Range: 
n = 1-6 
m = 0-7     
i = 1-2    
r = -10.00 to +10.00 
Default: 
n/a 
Response: 
n/a  
 
See Also: 
[ \ANO ], NTIO, \TANO, \TIO 
6K 5.3 
    
Use the 
\ANO
 command to set the voltage of an OPTO22 analog output. The maximum output range can be set from –
10.00 VDC to +10.00 VDC.  The 6K controller does not recognize the voltage range set on the I/O device (i.e., an 
\ANO
 
setting of +10 VDC is allowed for an analog output configured with a maximum limit of +5 VDC.) 
The controller addresses the OPTO22 I/O locations as follows: 
Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute 
32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered 
1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2. 
Digital
Input
Module
Input
1
0
Input
2
Input
3
Input
4
Digital
Input
Module
Input
1
1
Input
2
Input
3
Input
4
Digital
Output
Module
Output
1
2
Output
2
Output
3
Output
4
Digital
Output
Module
Output
1
3
Output
2
Output
3
Output
4
Analog
Output
Module
Output
1
4
Output
2
Analog
Output
Module
Output
1
5
Output
2
Analog
Input
Module
Input
1
6
Input
2
Analog
Input
Module
Input
1
7
Input
2
EXAMPLE: OPTO22 is Network Server #2
2\0IN.3
2\3OUT.2
2\5ANO.1
2\7ANI.2
 
Example: 
2NTIP2,172,54,125,34  ; Identify network server #2 as an OPTO22 unit at IP address  
; 172.54.125.34 
2NTCONN1 
; Attempt a connection to network server #2 (OPTO22 unit) 
2\4NTIO4 
; Server #2 (OPTO22), module #4 is an analog output module 
2\5NTIO4 
; Server #2 (OPTO22), module #5 is an analog output module 
2\4ANO.1=4.8 
; On Server #3, module #4, set the voltage on analog output #1 to  
; +4.8 VDC 
 
 
 
page 35