 iRIS 220 / iRIS 320, V1.19 User Guide  
 
Partial Power Save 
With  the  power  management  mode  set  to  partial  save,  the  on-board  LEDs  are  disabled  but  the  internal 
wireless modem remains in the fully active state as with the no power save mode. 
 
Full Power Save 
When power management is set to full save mode, the internal LED’s are disabled and the internal wireless 
modem remains in a powered off state until a GPRS/CDMA-1X or CSD or SMS session is activated.   
 
NOTE: While the modem is in this state, it is not possible to obtain signal strength measurements or 
interrogate the modem via the AT command set using the Modem Terminal mode.  
 
Additional power management features that operate in all modes include: 
 
 
Deactivation of RS232 driver ic when the DSR signal is not present. 
 
Disabling the LCD and turning off the backlight after two minutes of no activity. 
 
Ability to activate a GPRS/CDMA-1X session at scheduled times of day for pre-set period. 
 
 
2.8.5 Data Logging 
The  iRIS  supports  the  logging  of  data  from  six  virtual  sensors,  plus  a  further  three  internal  data  sources 
(battery  voltage,  supply  voltage  and  logger  temperature).    Each  of  the  six  virtual  sensors  can  obtain 
information from one of the following data sources: 
 
 
Analog Input 1 
 
Analog Input 2 
 
Analog Input 3 
 
Analog Input 4 
 
Pulse Counter attached to Digital Input 1 
 
Pulse Counter attached to Digital Input 2 
 
Simulated Pulse Counter enabled by Digital Input 1 
 
Simulated Pulse Counter enabled by Digital Input 2 
 
Frequency Counter attached to Digital Input 1 
 
Frequency Counter attached to Digital Input 2 
 
Up/down Counter attached to Digital Inputs 1 & 2 
 
Received Signal Strength Indication  (RSSI) 
 
Internal Database Location (for data obtained via user script or communications link) 
 
High-speed Serial Instrument (Unidata format) 
 
SDI-12 serial channel  
 
Each sensor can be set up to scale the raw data source into engineering units through the application of a 
multiplier and offset (slope and constant).  The scaled value can be logged to non-volatile memory at rates 
between  once  per  minute  to  once  per  hour  or  on  event  for  pulse  inputs.    As  all  logged  data  is  stored  in 
integer format, a logging multiplier is applied to the scaled value to maintain resolution. See Section 
4.3.9. 
 
It is also possible to configure a sensor to also log minimum, maximum, standard deviation or a calculated 
flow  rate  (pulse  source  only)  values.  See  the  next  section,  Section  2.8.6  and  also  Section  4.3.9  for  further 
details on configuring these extended logging features as part of the Sensor Cfg menus.