Optiquest iRIS 220 사용자 설명서

다운로드
페이지 73
37 
-
 iRIS 220 / iRIS 320, V1.19 User Guide  
 
Option 2 
When this option is selected you will be prompted to select the switching polarity of the output. This relates to 
the output’s electrical state with respect to its logical on/off state.   
 
If the polarity setting is 0 (normal), the output will actively pull down to 0V when the output logical state is on 
and be high impedance (open-circuit) when the output is logically off. 
 
If the polarity setting is 1 (inverted), the output will be high impedance (open-circuit) when the output logical 
state is on and be actively pulled down to 0V when the output is logically off. 
 
> Polarity (0:Normal 1:Inverted)= 
 
 
Option 3 
When this option is selected you will be prompted to enter a number representing the operating mode of the 
output. 
 
> Mode (0..5)= 
 
Valid modes are: 
 
Source 
Description 
Follow GPRS/CDMA/CSD Link State. I.e. Output is on if communication link is on-line. 
Follow Schedule as defined by the settings in options 3-6. 
Remote Control from Base.  DO1 is controlled by bit 0 of d1000, DO2 by bit 1 of d1000. 
Low Trigger. Activate when Sensor 1 last logged value <= trigger setpoint and trigger enabled.  
High Trigger. Activate when Sensor 1 last logged value >= trigger setpoint and trigger enabled.  
Force output permanently on. Required for both outputs if Unidata high-speed encoder used.  
 
NOTE:  If  DO1  is  set  to  mode  1  (Schedule)  it  will  be  forced  on  while  a  user  is  logged  on  via  the 
LCD/keypad interface.  This is to power up a controlled sensor for calibration purposes.  
 
 
Option 4 
When this option is selected you will be prompted to enter the length of time in seconds that you want the 
iRIS to keep the output energised if the mode is set to 1 (Schedule). 
 
> Duration (sec)= 
 
Option 5 
When  this  option  is  selected  you  will  be  prompted  to  enter  the  length  of  time  in  minutes  between  the 
successive operations of the output if the mode is set to 1 (Schedule). 
 
> Frequency (min)= 
 
Option 6 
When this option is selected you will be prompted to enter a string representing the time at which the iRIS is 
allowed to start controlling the output if the mode is set to 1 (Schedule). 
 
> Start Time (HHNN)= 
 
Option 7 
When this option is selected you will be prompted to enter a string representing the time at which the iRIS 
must stop controlling the output if the mode is set to 1 (Schedule). 
 
> End Time (HHNN)= 
 
NOTE:  See  Section  4.3.7,  titled  GPRS/CDMA-1X  Schedule  Cfg  for  details  on  how  these  parameters 
configure the schedule operation.