Typical Scheduled Output Example 
A ground water site using an iRIS 320 is required to log a sample every hour that is obtained from a pressure 
transducer  whose  power  supply  is  controlled  from  the  digital  output,  DO1  via  a  transistor  switch.  The 
transducer needs to be powered up for one minute prior to the measurement being taken and logged. The 
settings required for DO1 to achieve this are shown below. 
 
* Digital Output 1 Setup 
0 Exit 
1 Enable [Yes] 
2 Polarity [Normal] 
3 Mode [Schedule] 
4 Duration [65 sec] 
5 Frequency [60 min] 
6 Start Time [0059] 
7 End Time [2359]
 
 
The output will be activated at the beginning of the 59
th
 minute of each hour in the day, starting at 00:59. It 
will remain on for 65 seconds, ensuring that the sensor is still powered up at the point when the reading is 
captured  on  the  hour.    The  final  output  activation  for  the  day  will  occur  at  23:59  in  preparation  for  the 
midnight measurement. 
 
 
4.3.14 Date/Time Cfg (Level 2) 
The  Date/Time  Cfg  menu  is  where  the  various  time  functions  are  configured.    These  include  date,  time  of 
day, date format, time zone offset and clock trim. 
 
*  Date / Time 1 Cfg 
0  Exit 
 
 
 
 
1  Date [02 Sep 2005] 
2  Time [14:23:49] 
3  Date Format [0: DD Mmm YYYY] 
4  Time Offset [UTC +12hrs] 
5  Clock Trim [-1] 
 
 
  
Option 1
 
When this option is selected you will be prompted to enter the current local date as a string containing four 
digits for year, two digits for month and two digits for day.  All 8 digits must be entered. 
 
> Date (YYYYMMDD)= 
 
 
Option 2 
When this option is selected you will be prompted to enter the current local time as a string containing two 
digits for hour, two digits for minute and two digits for second. All 6 digits must be entered. 
 
> Time (HHMMSS)= 
 
 
Option 3 
When  this  option  is  selected  you  will  be  prompted  to  select  the  date  format  as  used  throughout  the  iRIS 
(LCD screens and terminal menus).  Enter a number to select the desired format. 
 
> Date Format 
(0=d mmm yyyy, 1=d/m/yyyy, 2=d/m/yy, 3=m/d/yy, 4=m/d/yyyy)=