Troubleshooting
‹
General Faults and Alarms
Faults and Alarms indicate unsusal inverter / application conditions. 
An alarm does not necessarily switch off the inverter but a message is displayed on the keypad (i.e.
a flashing alarm code) and an alarm output can be generated at the multi-function outputs (H2-01
and H2-02) if programmed. An alarm automatically disappears if the alarm condition is not present
anymore.
A fault switches the inverter output off immediately, a message is displayed on the keypad and the
fault output is switched. The fault must be reset manually after the cause and the RUN signal have
been removed.
The following table shows a list of faults and alarms with their corrective actions.
 Display
Alarm
Fault
Meaning
Corrective Actions
BUS
Option Com Err

Option Card Communication Alarm
After initial communication was established, the 
connection was lost. 
Check the connections and all user-side soft-
ware configurations.
CF
Out of Control

Control Fault
A torque limit was reached continuously for 3 
seconds or longer during a deceleration stop in 
Open Loop Vector control 
Check the motor parameters
CPF00
COM-
ERR(OP&INV)

Digital Operator Communication Fault 1/2
• Communication fault between Operator and 
Inverter
• CPU External RAM Fault
• Disconnect the Digital Operator and then 
connect it again.
• Cycle the Inverter power supply.
• Replace the Inverter.
CPF01
COM-
ERR(OP&INV)
CPF02
BB Circuit Err

CPF02 Fault
Baseblock circuit error
• Perform an initialization to factory defaults.
• Cycle the Inverter power supply.
• Replace the Inverter.
CPF03
EEPROM Error

CPF03
EEPROM error
CPF04
INternal A/D Err

CPF04
CPU Internal A/D Converter Fault
DEV
Speed Deviation

F1-04 = 0, 1 or 2 and A1-02 = 1 or 3
The speed deviation has been greater than the 
setting in F1-10 for a time longer than the setting 
F1-11.
• Reduce the load.
• Lengthen the acceleration and deceleration 
time
• Check the mechanical system
• Check the settings of F1-10 and F1-11
• Check the sequence and if the brake is 
opened when the inverter starts to increase 
the speed.

F1-04 = 3 and A1-02 = 1 or 3
The speed deviation has been greater than the 
setting in F1-10 for a time longer than the setting 
F1-11.
EF
External Fault

Forward/Reverse Run Commands Input 
Together
Both the forward and the reverse run commands 
are input simultaneously for 500ms or more. 
This alarm stops the motor.
Check external sequence logic, so that only 
one input is activated at a time. 
EF0
Opt External Flt

External fault input from Communications 
Option Card
• Check for an external fault condition.
• Verify the parameters.
• Verify communication signals
EFx
Ext Fault Sx


External fault at terminal Sx (x stands for termi-
nals S3 to S7)
Eliminate the cause of the external fault con-
dition. 
Ext Run Active
Cannot Reset

Detected after a fault when a RESET command 
is input while the RUN command is still active
Remove the RUN signal first and reset the 
error.
GF
Ground Fault

Ground Fault
The ground current at the Inverter output 
exceeded 50% of the Inverter rated output cur-
rent and L8-09=1 (Enabled).
• Remove the motor and run the Inverter 
without the motor.
• Check the motor for a phase to ground 
short.
• Check the output current with a clampmeter 
to verify the DCCT reading.
• Check the control sequence for wrong 
motor contactor signals.