EN-19
E1-04
Max. output 
frequency 
(FMAX)
To set V/f characteristics in a straight 
line, set the same values for E1-07 
and E1-09. In this case, the setting for 
E1-08 will be disregarded.
Always ensure that the four frequen-
cies are set in the following order:
E1-04 (FMAX) 
 E1-06 (FA) > E1-07 
(FB) 
 E1-09 (FMIN)
E1-05
Max. output 
voltage 
(VMAX)
E1-06
Base fre-
quency (FA)
E1-13
Base Voltage
(VBASE)
Motor Data Settings
E2-01
Motor rated 
current
Sets the motor data.
E2-02
Motor rated 
slip
E2-03
Motor no-load 
current
E2-04
Number of 
motor poles
E2-09
Motor 
mechanical 
losses
E2-11
Motor rated 
output power
PG Option Setup
F1-01 PG constant
Sets the number of PG pulses per 
revolution
F1-05 PG rotation
0:Phase A leads with forward run 
command
1:Phase B leads with forward run 
command
Digital I/O Settings
H1-01 
to 
H1-05
Terminal S3 to 
S7 function 
selection
Refer to 
 for a 
list of selections
H2-01 
and
H2-02
Terminal M1-
M2 and M3-
M4 function 
selection
Refer to 
 for a list of selections
Analog I/O Settings
H3-08
Analog input 
A2 signal level 
selection
Selects the signal level input at multi-
function analog input A2.
0:0 to +10 V (11 bit).
1:-10 to +10 V 
2:4 to 20 mA (9-bit input).
Ensure to switch S1-2 to “V” before 
using a voltage input. 
H3-09
Analog input 
A2 function 
selection.
Selects the multi-function analog 
input function for terminal A2. 
Param-
eter 
Num-
ber
Name
Description
Output Voltage (V)
Frequency (Hz)
H3-13
Terminal A1/
A2 switching
Selects on which terminal the main 
frequency reference can be input.
0:Use analog input 1 on terminal 
A1 for main frequency reference.
1:Use analog input 2 on terminal A2 
for main frequency reference.
H4-01
Terminal FM 
monitor selec-
tion
Sets the number of the monitor item 
to be output (U1-
††
) at terminal FM/
AM.
H4-04
Terminal AM 
monitor selec-
tion
Pulse Train I/O
H6-01
Pulse train 
input function 
selection
Selects the pulse train input function
0:Frequency reference
1:PID feedback value
2:PID target value
H6-02
Pulse train 
input scaling
Sets the number of pulses in Hz that 
is equivalent to 100% of the input item 
selected in H6-01.
H6-06
Pulse train 
monitor selec-
tion
Selects the pulse train monitor output 
item (U1-
††
)
H6-07
Pulse monitor 
scaling
Sets the number of pulses output in 
Hz when the monitor item is 100%.
Stall Prevention 
L3-01
Stall preven-
tion selection 
during accel
(not available 
in CLV)
0:Disabled (Acceleration as set. 
With a heavy load, the motor may 
stall.)
1:Enabled (Acceleration stopped 
when L3-02 level is exceeded. 
Acceleration starts again when the 
current has fallen below the stall 
prevention level).
2:Intelligent acceleration mode (Using 
the L3-02 level as a basis, accelera-
tion is automatically adjusted. Set 
acceleration time is disregarded.)
L3-04
Stall preven-
tion selection 
during decel
0:Disabled (Deceleration as set. If 
deceleration time is too short, a 
DC bus overvoltage may result.)
1:Enabled (Deceleration is stopped 
when the DC bus voltage exceeds 
the stall prevention level. Decelera-
tion restarts when the voltage falls 
below the stall prevention level 
again.)
2:Intelligent deceleration mode 
(Deceleration rate is automatically 
adjusted so that the Inverter can 
decelerate in the shortest possible 
time. The set deceleration time is 
disregarded.)
3:Enabled with braking resistor
Fault Restart
L5-01
Number of 
auto restart 
attempts
Sets the number of auto restart 
attempts.
Automatically restarts after a fault and 
conducts a speed search from the run 
frequency.
L5-02
Auto restart 
operation 
selection
Sets whether a fault relay is activated 
during fault restart.
0:No output (Fault relay is not acti-
vated.)
1:Output (Fault relay is activated.)
Param-
eter 
Num-
ber
Name
Description