The Triggers
 
 
 
 
   
44 
6.8.1 Digital Input 
The digital input reads the digital input of an external sensor device that is connected to the GPI/O 
port, and can be defined: 
  With Pullup: the system can detect either a short circuit (activating the Hi to Lo trigger – 
closed circuit) or no short (activating the Lo to Hi trigger – open circuit) using the internal 
pull-up resistor. The threshold levels are not relevant in this case and will be automatically 
adjusted and locked to their appropriate levels 
For example, an alarm closing a circuit that activates a series of actions  
  Without Pullup: the system detects the voltage levels and translates them to High or Low 
according to the user defined threshold levels. 
For example, a high temperature alarm that exceeds the maximum voltage threshold 
Setting the Digital Input  
In this example, an alarm setting causes a short circuit, thus activating a trigger. 
To set the trigger: 
1.  Define the GPI/O in the port manager. 
Check Pullup for short circuit detection; the threshold is set automatically (skip step 2): 
 
Do not check Pullup for voltage level detection; the threshold to be set by the user (proceed to 
step 2): 
 
2.  Define the GPI/O threshold (minimum from 0 and maximum up to 30V) according to the 
indication set by the device
. 
 
Figure 87: GPI/O Threshold Window 
3.  Click the Add GPI/O Trigger (in the Trigger area) and select the GPI/O port (GPI/O 1 or 2 in 
this example).  
The following window appears: 
 
Figure 88: GPI/O Trigger Properties Window for Digital Input 
                                                        
1
 Other voltages will not activate the trigger