3.
INSTALLATION
Installation of the fire detection and alarm system must comply with the current editions of:
!
 
The IEE wiring regulations.
!
 
The British Standard for Fire Detection and Alarm Systems for buildings BS 5839: part 1
!
 
Local country legislation if outside of the United Kingdom.
Take care not to install the cables in the proximity of high voltage cables or in areas likely to induce electrical
interference. Junction boxes should be avoided, but if they have to be installed then they must be clearly
labelled "FIRE ALARM".
Special attention should be made in the selection of loop wiring conductor size to ensure that the voltage drop
does not prevent devices operating within their specification even under minimum supply and maximum load
conditions. Consideration should also be given for future expansion of the system.
It is not permissible to run more than one detection loop in single cable, but a four-core cable can be used for
the feed and return of an individual loop. However, to increase the integrity of the loop it is recommended that
the feed and return cable pairs use different paths around the building.
It is not permissible to run any other circuits in the same cable as a detection loop, i.e. sounder circuits, power
supplies, plant shut downs etc, as the induction capacities of the cable can cause corruption of loop information
and/or inter-loop "cross talk".
3.1
SYSTEM SCHEMATIC - Figure 2
Figure 2: System Schematic Diagram
The control panel has a number of internal 2.5mm terminals for connection to the external field cables.