Care must be taken to ensure metal filings or swarf does not fall onto the printed circuit boards. An adequate
number of pre-formed knockouts have been provided on the top of the enclosure so there should be no
requirement to drill any additional holes. Ensure that if a knockout is removed and unused, that the hole is filled
with a good quality cable gland that is securely blanked off.
3.4 ENCLOSURE 
MOUNTING
The control panel should be installed within the building to be protected at a prominent location and at a height
where it can be easily accessed during an emergency. The control panel should ideally be located in the
entrance, foyer or hallway of the building at eye level. The panel should not be positioned where conditions may
affect its performance. Areas prone to salt air, moisture, high humidity, physical abuse, and extreme
temperatures should be avoided.
Remove the control panel from its packing and unlock the door using the Allen Key provided.
Note, A spare parts bag is not provided with this control panel. Battery leads and End of Line resistors are
factory fitted to the associated output terminals. A spare sounder fuse is provided. Refer figure 2 for location.
Hold the panel to the wall at the desired mounting height and mark the position of the top centre keyhole. The
enclosure fixing positions are shown in figure 4. The keyhole is provided on the backbox to allow the panel to be
hooked onto the wall whilst the remaining four screws are located, marked and drilled accordingly. Secure the
panel to the wall using suitable fixings such that adequate support is provided.
Figure 4: Enclosure Fixing Positions