HP Performance Optimized Data Center (POD) 40cp 사용자 설명서

다운로드
페이지 63
 
Optional components  44 
Optional components 
Additional insulation 
You can choose to have additional insulated paint added to your HP POD prior to shipment. The 
additional insulation will enable the HP POD to function properly in temperatures as low as -29°C (-20°F). 
 
Air filter sensor 
The air filter sensor is an optional component that, if installed, alerts you to change your air filters. The 
sensors are located near each of the 12 air filters. If the air filters are full and should be replaced, an alert 
will be sent via your BMS. 
 
Humidifier (optional) 
If you choose to connect to the humidifier, it maintains the humidity within the HP POD within a set range, 
according to ASHRAE standards.  
Maintaining the humidity helps to minimize static electricity within the HP POD. 
For more information about the humidifier, see the product documentation included in the Operations & 
Maintenance Manual ("
 
Fire protection system 
The fire protection system is a HP POD self-contained system, with no connection to your BMS. The fire 
protection system consists of 12/30 pre-em novac, a clean agent fire suppressant, eliminating the need 
for additional water to be connected to the HP POD in case of a fire emergency. 
 
HP POD security 
Routing raceways for the following security options are provided by HP and can be installed as a custom 
service option. You are responsible for providing additional hardware, cabling, and controllers to support 
these options. 
Security options: 
 
Key lock hardware—Standard security provided 
 
Card reader security—Junction boxes provided at every entrance to upgrade security, if desired. 
 
Magnetic or electronic locks—Prewiring provided at every entrance to upgrade security, if desired. 
Magnetic or electronic locks are not provided. 
 
Internal/external cameras—Camera mounting locations are provided along with empty conduit and 
pull drag lines.