Site requirements  7 
 
Cooling water 
 
Power 
 
Drain (optional) 
 
Available to connect to central facility infrastructure 
 
BMS via BacNet protocol 
 
Security system 
 
Convenience outlet power 
 
Site networking connection 
 
Domestic water for humidifier (optional) 
 
Transformer, switchboard, and water distribution kit locations 
If you choose to purchase the kits, consider: 
 
Distance from the facility utilities 
 
Distance from the HP POD 
The transformer and switchboard can be installed within 3 m (10 ft) of the HP POD during normal 
installation. The transformer and switchboard can be installed over 3 m (10 ft) from the HP POD, but this 
requires additional planning and costs. HP recommends installing the transformer and switchboard no 
more than 30 m (98 ft) from the HP POD. 
The water distribution kit can be installed within 3 m (10 ft) of the HP POD during normal installation. The 
water distribution kit can be installed over 3 m (10 ft) from the HP POD, but this requires additional 
planning and costs. HP recommends installing the water distribution kit no more than 30 m (98 ft) from 
the HP POD. 
HP POD connection locations 
 
 
Callout Connection 
Main input power junction box