Site requirements  8 
Callout Connection 
Chilled water return connection 
Chilled water supply connection 
IT cable portals∗ 
There are identical IT cable portals on the left side of the HP POD. 
 
 
Work space requirements 
  
 
IMPORTANT:
  Failure to comply with the work space requirements can result in failed 
authorization to power your HP POD by local electrical inspectors.  
  
 
Work platform requirements 
  
 
NOTE:
  The base of the work platform should be level with the base of the HP POD. If you 
choose to leave the HP POD on a trailer, a work platform is required. 
  
The area outside of the HP POD directly in front of the panels must have a work platform. The 
specifications of the work platform are: 
 
The work platform must be a minimum of 1 m (3 ft) wide for standard platforms, and 1.1 m (3.5 ft) 
wide if the work platform is constructed of grounded metal. 
 
The work platform surface must be <2.0 m (6.6 ft) from the center of any circuit breaker actuator 
handle. 
 
Work space lighting 
Make sure that the HP POD, transformer, switchboard, and water distribution kit are installed in a well lit 
area that complies with local work space lighting requirements, per code regulations. 
 
Environmental considerations 
 
Install a properly engineered awning to enable access to the building in adverse weather conditions. 
 
Install lightning protection for the HP POD. 
 
Make sure that the HP POD is properly grounded. 
 
Avoid placing the HP POD directly along a drainage path or in an area prone to flooding. 
 
Raise the HP POD slightly off the ground, or set it on a higher point of elevation. In low elevated 
areas, HP recommends setting the HP POD on a concrete housekeeping pad. 
 
Avoid placing the HP POD directly in the path of external heat loads such as a diesel generator or 
an air cooled chiller. 
 
Temperature considerations 
The standard operating temperature for the HP POD is from -17.8°C to 54.4°C (0°F to 130°F). 
If you choose to purchase the additional insulating paint ("
operating temperature of the HP POD is from -28.9°C to 54.4°C (-20°F to 130°F).