Power, electrical, and controls  31 
 
Non-redundant power installation (1N load)—Both busways are powered from the same power feed. 
 
 
Redundant power installation (2N load)—Each busway is powered from parallel power paths from 
independent power feeds. 
 
 
Drop boxes 
The internal electrical busways provide a location to connect each of the drop boxes, which then power the 
PDUs. Stagger the drop boxes on the electrical busways by connecting one drop box to busway #1 and 
connecting the next drop box to busway #2. A staggered configuration enables load balancing with the rack 
equipment and is necessary to ensure redundancy.