HP Performance Optimized Data Center (POD) 20cp 사용자 설명서

다운로드
페이지 86
 
Power, electrical, and controls  33 
 
Feature 
Specification 
Rack type 
HP POD rack 
Max number of racks 
10 
Max U space per rack 
50U 
Max U space per HP POD 20c 
500U 
Server capacity 
288 kW power capacity 
Average capacity per rack 
28.8 kW 
Peak capacity per rack 
69 kW 
Voltage to rack 
200-240 VAC 
Rack configuration 
Redundant/Non-redundant 
capabilities 
Total number of PDU's 
20 (two per rack) 
Max power per PDU 
30 A = 17 kW; 60 A = 34 kW 
Max load (Chilled POD cooling mode)
*
  288 kW 
Airflow per rack (Chiller POD cooling 
mode) 
1,700 CFM 
 
*
Dependent on configuration 
 
HP POD 20c lighting 
The HP POD 20c includes six LED lights. Three lights are located in the cold aisle and three lights are located 
in the hot aisle. 
The main light switch is located on the ECS control panel door. For more information on the light switch 
location, see "Life safety component identification (on page 
)." 
Two of the six lights are connected to battery backup power, keeping the interior of the HP POD 20c 
illuminated during a power outage or emergency. 
For more information on lighting, see the HP Performance Optimized Datacenter 20c Maintenance and 
Service Guide