4 Parameter indices of the equipment parameters
For a request and/or transmission of data from and/or to the R2600/01, not only the parameter index for the individual data but also the format and 
thus the length of the data block in the long set are of interest. From the column "Format" of the parameter tables and section 2.4.4, the number, order 
and contents of the characters of the data block can be found. 
See the operating instructions for detailed information on the function of the data.
4.1 Temperature parameters
The temperature parameters are combined in the main parameter group 0. 
In the R2600/01, they are stored in standardized form to the measuring range so that other values result when the sensor type or the unit of measure 
is re-configured, or when a change is made from fixed value or slave controller to differential controller.
4.1.1
Table of temperature parameters 
X1 = range span, X2 = upper range limit, MBU = X2 - X1, see 4.1.3
PI
Parameter
Display
Format
Unit
Setting range
Remarks
00h
Set point
± 15 bits
(4.1.2)
 SP L... SP H
01h
High limit for relay A1
± 15 bits
(4.1.2)
0 = oFF, 1... MBU
At rel. limit
 X1 = oFF, X1 + 1 ... X2
At abs. limit and 
fixed value controller
–MBU/2 = oFF,
–MBU/2 + 1 ... +MBU/2
At abs. limit and 
differential controller
02h
Low limit for relay A1
± 15 bits
(4.1.2)
Same as PI = 01h
Same as PI = 01h