Fujitsu DX60S2 사용자 설명서

다운로드
페이지 62
Chapter 3  Connections
  3.3  Power Supply Connection
ETERNUS DX60 S2 Disk storage system User’s Guide -Site Planning-
46
Copyright 2012 FUJITSU LIMITED
P3AM-5492-04ENZ0
LAN for remote support
Various failures that occur in the ETERNUS DX Disk storage system are notified to the remote 
support center. Remote support connection can be separated from the LAN for operation man-
agement.
3.3
Power Supply Connection
Connect the power cords (AC cables) of the ETERNUS DX Disk storage system to the power 
sockets, the UPS sockets, or the power control unit sockets.
Refer to 
 for details about the types and the number 
of power outlets/sockets.
3.3.1
Input Power Supply Lines
Multiple power supply facilities in the building or UPS units are recommended for power supply 
redundancy. When the ETERNUS DX Disk storage system power supply is redundantly config-
ured, business can continue even if one of the power lines fails.
To connect the ETERNUS DX Disk storage system to power supply facilities, use the following 
configurations to improve the availability of the power supply facilities if a power supply facility 
failure occurs.
Connect the power cords of PSU#0 and PSU#1 to different lines.
When a power distribution unit is used, separately connect it to line 0 (PSU#0) and line 1 
(PSU#1).
Alternatively, optimal system design (including the server) may instead lead to the ETERNUS DX 
Disk storage system being configured with only a single power supply facility or UPS unit. Which 
configuration is selected will depend on system availability requirement considerations.
Figure 3.6
Dual-line power supply when connecting to power sockets
Two power supply units (PSU#0 and PSU#1) are installed in each enclo-
sure. Make sure that power cords are connected to both of the power sup-
ply units. 
Power distribution unit
ETERNUS DX
Disk storage system
P
o
w
er supply
facility
Line 1
Line 0
PSU
PSU
P
o
w
er supply
facility