Chapter 3  Connections
  3.3  Power Supply Connection
ETERNUS DX60 S2 Disk storage system User’s Guide -Site Planning-
48
Copyright 2012 FUJITSU LIMITED
P3AM-5492-04ENZ0
3.3.2
UPS Connection
It is recommended that an Uninterruptible Power Supply System (UPS) be used as the power 
supply source for the ETERNUS DX Disk storage system to cope with power outages and 
momentary voltage drops in the normal power supply.
Note that when connecting an ETERNUS DX Disk storage system to a UPS with one power sup-
ply line, the total value of the power requirements for all the enclosures must not exceed the UPS 
output capacity.
When one of the power supply lines fails for redundantly configured UPS units with two power 
supply lines, all of the power for the ETERNUS DX Disk storage system must be supplied from 
the other line. Select a UPS that can supply sufficient power so that the total value of the power 
requirements does not exceed the UPS output capacity in case only one power supply line is 
available.
For details about the necessary UPS output capacity, refer to the specifications of the UPS that 
is used.
A UPS must satisfy the following conditions:
Rating capacity
Secure a sufficient rating capacity for the total value of the maximum power requirements for 
the enclosures that are to be installed. 
For the maximum power requirements of each enclosure, refer to 
Supply time
Consider the power supply time of the battery to make sure that the ETERNUS DX Disk 
storage system power is not turned off before the server shuts down.
Socket type
If the power plug type and the socket type of the UPS do not match, it is necessary to equip 
the UPS (AC output) with an appropriate type of socket. Request a qualified electrician to 
perform the necessary work to make terminal block connections available.
Power supply configuration
If a UPS is used, make sure that it supplies power to all the enclosures.
Configurations where the controller enclosure is powered by the UPS while the drive 
enclosure is powered directly from AC are not supported.