7.1.2 Technical
Data
MultiCom CCC hardware data
(assembly A29.1)
Connector :
Port 1 RS232 for configuration
and
COM
server
connection
X2:
9-pin
D-sub
(socket;
insulated)
Port 2 RS232/RS485 for Modbus
X5:
9-pin
D-sub
(socket;
insulated)
RS485 connection:
Twisted pair with Data+, Data-,
shielded,
shield
attached
on
one
side
Distance:
1200 m max. at 9600 baud
Bus stations:
Max. 32
Data line:
Shielded 1:1 data line
(2 x 0.22; twisted pair),
e.g. Lapp "UNITRONIC-BUS LD"
(2 x 0.22; twisted pair),
e.g. Lapp "UNITRONIC-BUS LD"
Port 3 CAN bus for remote panel
X4:
3-pin
Combicon
connector
Communication data port 1 (X2)
Protocol:
CBSER
Transmission rate:
1200 - 57,600 baud (adjustable)
Transmission parameters: 9600 baud, 8, E, 1 (default)
Configuration mode: 9600 baud, 8, N, 1
Configuration mode: 9600 baud, 8, N, 1
Communication data port 2 (X5)
Protocol:
Modbus
Transmission mode:
Half-duplex
Transmission code:
RTU
Transmission rate:
1200 - 57,600 baud (variable)
19,200 baud (default)
Start bits:
1
Data bits:
8
Parity:
none,
even, odd (variable)
Stop bits:
2 with no parity, 1 with parity
Function code:
03 (read register)
06
(write
register)
16
(write
multiple
registers)
Min. response time of slave: 0-99 ms variable (0 ms default)
Modbus slave address:
Modbus slave address:
01-99 (adjustable) (01 default)
Communication data port 3 (X4)
Protocol:
Proprietary
CAN
bus
Transmission rate:
50 kbaud