Geo Brick LV User Manual
 
MACRO Connectivity 
 233 
 
The current loop feedback address Ixx82 should be set per the following table: 
MACRO 
motor 
Motor # 
Ixx82 
Register 
 
MACRO 
motor 
Motor # 
Ixx82 
Register 
1
st
 
5 or 9 
$078422 
Servo Node 0   
5
th
 
9 or 13 
$078432 
Servo Node 8 
2
nd
 
6 or 10 
$078426 
Servo Node 1   
6
th
 
10 or 14  $078436 
Servo Node 9 
3
rd
 
7 or 11 
$07842A  Servo Node 4   
7
th
 
11 or 15  $07843A 
Servo Node 12 
4
th
 
8 or 12 
$07842E 
Servo Node 5   
8
th
 
12 or 16  $07843E 
Servo Node 13 
 
 
Commutation Cycle Size 
Ixx70 = {Number of pair poles} 
Ixx71 = {Number of counts per revolution * 32
 
 
I2T Settings (example for motor #9): 
I15=0 
 
 
 
; Trigonometric calculation in degrees 
#define MaxPhaseFreq 
P8000  ; Max Phase Clock [KHz] 
#define PWMClk 
 
P8001  ; PWM Clock [KHz] 
#define PhaseClk 
 
P8002  ; Phase Clock [KHz] 
#define ServoClk 
 
P8003  ; Servo Clock [KHz] 
MaxPhaseFreq=117964.8/(2*I6800+3) 
PWMClk=117964.8/(4*I6800+6) 
PhaseClk=MaxPhaseFreq/(I6801+1) 
ServoClk=PhaseClk/(I6802+1) 
 
#define Mtr9ContCurrent 
; Continuous Current Limit [Amps] –User Input 
#define Mtr9PeakCurrent 
; Instantaneous Current Limit [Amps] –User Input 
#define MaxADC 
 
16.3 
; See Geo MACRO electrical specifications –User Input 
#define Mtr9I2TOnTime 
; Time allowed at peak Current [sec] 
 
I957=INT(32767*(Mtr9ContCurrent*1.414/MaxADC)*cos(30)) 
I969=INT(32767*(Mtr9PeakCurrent*1.414/MaxADC)*cos(30)) 
I958=INT((I969*I969-I957*I957)*ServoClk*1000*Mtr9I2TOnTime/(32767*32767)) 
 
19.  Current-Loop Tuning (Ixx61, Ixx62, Ixx76) 
Current  loop  tuning  is  performed  in  the  same  manner  as  it  would  be  for  any  digitally  commuted 
amplifier. A satisfactory current loop response (PmacTuningPro2 screen shot) would look like: