Bryan Boilers Forced Draft Steam Boilers 사용자 설명서

다운로드
페이지 37
 
 
 
 
 
 
 
 
 
 
 
 
 
                                                                                                                                             
1.8.7 ACCEPTABLE VENT TYPES
 
 
LISTED GAS VENTS 
Listed gas vents must be applied only on those 
applications for which they are listed. Type B gas 
vents are NOT listed for use on forced draft 
appliance vent systems. 
 
Installation of these vents must comply with the 
vent listing, with the vent manufacturer's 
instructions and with complete adherence to the 
codes and clearances as outlined previously. 
 
PRESSURIZED VENT SYSTEMS 
Some Bryan Boilers (unless specifically fitted for 
the application) are not suitable for operation on a 
pressurized vent systems. Refer to Section 2 of 
this manual for the allowable range of vent 
pressure for each series. The RV, RW, and AB 
series boilers are designed for pressurized vent 
systems. All others require a neutral pressure. 
 
SINGLE-WALL METAL PIPE 
Single-wall metal pipe must be of galvanized 
sheet or other approved non-combustible 
corrosion resistant material, with minimum 
thickness per Table 1.8.7, from the National Fuel 
Gas Code. Single-wall metal pipe should be 
insulated to prevent excessive heat in the boiler 
room and to avoid ignition and spillage problems 
as well as corrosion from excessive 
condensation. 
 
MASONRY, METAL AND FACTORY BUILT 
CHIMNEYS 
Installation of factory built vents and chimneys 
must comply with the vent listing, with the vent 
manufacturer's instructions and with adherence to 
the codes and clearances as outlined herein. 
Masonry or metal chimneys must be built and  
installed in accordance with nationally recognized 
building codes or standards. 
 
MASONRY CHIMNEYS FOR RESIDENTIAL 
APPLICATIONS MUST BE LINED WITH FIRE-
CLAY FLUE LINING (KX C315 OR THE 
EQUIVALENT) WITH THICKNESS NOT LESS 
THAN 5/16 INCH OR WITH A LINER OF OTHER 
APPROVED MATERIAL THAT WILL RESIST 
CORROSION, SOFTENING OR CRACKING 
FROM FLUE GASES AT TEMPERATURES UP 
TO 1800 F. 
EXISTING CHIMNEYS SHOULD BE 
INSPECTED FOR UNSAFE CONDITIONS, 
SUCH AS DETERIORATED MASONRY AND 
EXCESSIVE SOOT OR OTHER BLOCKAGE OR 
POTENTIAL BLOCKAGE. SEE ALSO SECTION 
1.8.6. 
 
EXISTING CHIMNEYS MUST BE PROPERLY 
SIZED FOR THE FLUE GAS LOADING TO BE 
USED. THAT IS, IF AN EXISTING CHIMNEY IS 
USED FOR A SMALLER TOTAL INPUT THAN 
ITS ORIGINAL DESIGN, A LINER OR VENT IS 
REQUIRED. THE USE OF A PROPERLY SIZED 
GAS VENT OR LINER WILL PREVENT 
DETERIORATION OF THE CHIMNEY DUE TO 
THE EXCESSIVE CONDENSATION WHICH 
RESULTS ON OVERSIZED SYSTEMS. 
 
                                                                  
WARNING
 
UNDER NO CIRCUMSTANCES SHOULD THE 
FLUE PIPE BE CONNECTED TO THE 
CHIMNEY OF AN OPEN FIREPLACE. 
                                                                  
TABLE 1.8.7A 
WATER BOILER & STEAM BOILERS TO 50 PSIG 
TABLE 1.8.7B 
(STEAM BOILERS OVER 50 PSIG) 
Diameter of  
Connector, Inches 
Minimum Thickness, 
Inch (Gauge) 
Diameter of 
Connector, Inches 
Minimum Thickness, 
Inch (Gauge) 
6 to 10 
0.023 (24) 
14 and less 
0.053 (16) 
10 to 12 
0.029 (22) 
14 to 16 
0.067 (14) 
12 to 16 
0.034 (20) 
16 to 18 
0.093 (12) 
16 + 
0.056 (16) 
18 + 
0.123 (10)