TABLE 1.8.1C: ESTIMATING FLUE GAS EMISSIONS
 
 
Estimated Emissions (Volumetric Flow Rate Per Million Btu/hr Input) 
(Multiply PPH listed times boiler input divided by 1,000,000) 
BOILER 
TYPE 
PARTICULATES NOx 
CO 
SOx Hydrocarbons 
 
PPH per 
MMBH 
PPM 
PPH per 
MMBH 
PPM 
PPH per 
MMBH 
PPM 
PPH per 
MMBH 
PPM 
PPH per 
MMBH 
PPM 
Gas Fired  
 
Oil Fired 
N/A 
 
0.020 
N/A 
 
20 
0.049 
 
0.068 
50 
 
70 
0.194 
 
0.018 
200 
 
18 
N/A 
 
0.286 
N/A 
 
290 
0.010 
 
0.004 
10 
 
 
 
1.8.2 CLEARANCES
 
 
The vent system and draft control devices must 
be installed so as to achieve the clearances to 
surfaces outlined in Table 1.2.1, Minimum 
Clearances chart, in this manual. See also Table 
1.8.9 for vent clearances. All clearances must 
comply with the National Fuel Gas Code 
(NFPA54), and with all  
local and state building codes. The clearances 
described in this manual are intended to be  
general guidelines only, additional requirements 
may occur because of local building design 
regulations. 
 
1.8.3 BOILER ROOM PRESSURIZATION
 
 
The boiler room must be supplied with adequate 
air for combustion and for proper operation of 
draft control devices (barometric dampers or draft  
diverters) as outlined in "Combustion Air Supply", 
Section 1.7 of this manual. 
 
                                                                                                                                            
WARNING
 
THE BOILER ROOM MUST BE MAINTAINED 
AT A POSITIVE OR NEUTRAL PRESSURE 
(RELATIVE TO OUTDOORS) AT ALL TIMES. 
EXHAUST FANS OR CONNECTIONS FROM 
THE BOILER ROOM TO ZONES OF NEGATIVE 
PRESSURE (AIR DUCTS, NEGATIVE 
PRESSURE ROOMS, ETC.) WILL CAUSE 
NEGATIVE PRESSURE IN THE BOILER 
ROOM. SUCH CONDITIONS WILL CAUSE 
HAZARDOUS OPERATION OF THE BOILER 
AND INTRODUCTION OF COMBUSTION 
PRODUCTS INTO THE BUILDING AIR. 
 
IF THE BOILER ROOM MUST BE UNDER A 
NEGATIVE PRESSURE AT ANY TIME, AN  
INDUCED DRAFT FAN WILL BE REQUIRED. 
FURTHER, THE BOILER MUST BE PROVIDED 
WITH A BAROMETRIC DRAFT CONTROL - 
NOT WITH A DRAFT DIVERTER. THE FAN 
MUST BE INTERLOCKED WITH THE BOILER 
AND A DRAFT PROVING SWITCH MUST BE 
INSTALLED TO PREVENT OPERATION OF 
THE BOILER IF THE FAN SHOULD FAIL TO 
OPERATE. 
 
IT ALSO MAY BE ADVISABLE TO INSTALL AN 
AUTOMATIC VENT DAMPER IN THE VENT 
SYSTEM TO PREVENT BACKFLOW 
THROUGH THE VENT SYSTEM DURING 
BOILER OFF CYCLES. SEE FOLLOWING 
SECTION ON AUTOMATIC VENT DAMPERS.