INSTALLATION
Thermostat installation and all components of the 
control system shall conform to Class II circuits per 
the NEC code.
WARNING
!
Control 40C01-1400
Control can be mounted on wall or equipment. Control has 
four mounting holes. Wall anchors and screws are provided 
for mounting on drywall. Drill 3/16 hole for drywall mounting.
If mounting on equipment 
Do Not Mount inside HVAC 
equipment. Only mount on outside of HVAC equipment.
WIRING CONNECTIONS 
Refer to equipment manufacturers’ instructions for specific 
system wiring information. After wiring, see CONFIGURATION 
section for proper thermostat configuration.
Connect wires as appropriate for HVAC systems (see wiring 
diagrams). To power control, connect the 24 V system hot to 
R terminal and common to C on left side of control labelled 
“Power”. On initial power up the 7 segment LED on the 
Thermostat / Interface 1F98-1491
1)  Pull the thermostat/interface off the base. Forcing or 
prying on the thermostat will cause damage to the unit. 
2)  Place base over hole in wall and mark mounting hole 
locations on wall using base as a template.
3)  Move base out of the way. Drill mounting holes. If you are 
using existing mounting holes and the holes drilled are 
too large and do not allow you to tighten base snugly, use 
plastic screw anchors to secure the base.
4)  Fasten base snugly to wall using mounting holes and two 
mounting screws. Leveling is for appearance only and will 
not affect thermostat operation. 
5)  Connect wires to terminal  block on base (see Figure 1). 
6)  Push excess wire into wall and plug hole with a fire 
resistant material (such as fiberglass insulation) to prevent 
drafts from affecting thermostat operation.
7)  Carefully line the thermostat up with the base and snap 
into place.
 R ......................................... 24 VAC Transformer 
 RC ....................................... 24 VAC Cooling Transformer
 RH ....................................... 24 VAC Heating Transformer
 C ......................................... 24 V Transformer Common
 W/E ..................................... Heating Stage 1
                                               HP Aux/Em Heat Stage 1
 W2 ....................................... Heating Stage 2
                                               HP Aux/Em Heat Stage 2 
 Y .......................................... Compressor Stage 1
 Y2 ........................................ Compressor Stage 2
G .......................................... Fan Relay
L Terminal ............................ System Monitor Compatible
                                               with Comfort Alert Diagnostics
O/B Terminal ........................ Changeover Relay Heat Pump
DHM .................................... Dehumidification Relay / Connection
DHM2 .................................. Dehumidification Relay / Connection
HM ....................................... Humidification Relay / Connection
HM2 ..................................... Humidification Relay / Connection
R .......................................... 24 VAC to Interface
1........................................... Data to/from Interface
2........................................... Data to/from Interface
C .......................................... 24 VAC Common to Interface
RJ11 .................................... Field configuration hook-up with RJ11
                                              equipped configuration tool
+ .......................................... Voltage to Outdoor Sensor
S .......................................... Outdoor Sensor Temperature Signal
- ........................................... Voltage to Outdoor Sensor
BLUE EASY INSTALL INPUTS/OUTPUTS
control  will display E (for communication error) until interface 
is connected. With power supplied to control, it is normal for 
the green system LED to flash periodically.  
With interface connected, the 7 segment LED will display 
C to indicate the two devices have initiated communication. 
C will disappear after approximately 30 seconds when 
communication is established.
Fig. 1 - Thermostat / Interface to control wiring
R
R
1
2
C
1
2
40C01Control
1F98 Thermostat
Easy Install 40C01               Operational / Functional
 Control Terminals
Easy Install 40C01               Operational / Functional
 Control Terminals
C