CONTROL CIRCUITS 
TMS7 SERIES 
ME00070B 
13 
Control Circuits 
6.1  Electrical Schematic
 
 
 FLC  SELECT
I43
I44
I11
I12
I21
I22
I33
R ESET
STOP
I34
START
OR
OR
C7
C6
4-20mA OUTPUT
(MOTOR CUR RENT)
PROGRAMMABLE
OUTPUT C
(Tripped)
RUN OUTPUT
R34
R33
L2B
L3B
L1B
E
T2
RS485 SERIAL
INTERFACE
GND
C5
C4
C3
R 43
R44
MOTOR
THERMISTOR
R24
R23
L1
L2
L3
T1
T3
A1
A2
A3
R 14
R12
R11
C1
C2
3 PHASE
SUPPLY
TO MOTOR
PROGRAMMABLE
OUTPUT B
(Start/Run)
PROGRAMMABLE
OUTPUT A
(Main  Contactor)
C24  models
230V
+10
-15
-15
+10
400V
C45  models
575V
+10
-15
-15
+10
460V
 
 
6.2  Control Supply 
 
Voltage must be connected to the TMS7 control voltage 
terminals. The required control voltage is dependent upon the 
TMS7 model ordered. 
• 
TMS7xxxx-xx-C24-xx models: 230VAC (A2-A3) or 400VAC 
(A1-A2) 
• 
TMS7xxxx-xx-C45-xx models: 460VAC (A1-A2) or 575VAC 
(A2-A3) 
 
TMS7 Model 
Maximum VA 
TMS7-4007~TMS7-4022 
11VA 
TMS7-4030~TMS7-4055 
18VA 
TMS7-4075~TMS7-4110 
24VA 
TMS7-4132~TMS7-4500 
41VA 
TMS7-4600~TMS7-4800 
56VA 
 
For circumstances where the available control supply voltage is 
not suitable for direct connection to the TMS7 the following 
range of auto-transformers are available as accessories. These 
auto-transformers can be mounted within the TMS7 in models. 
 
Part Number 
Input 
Voltages 
(C24 
Models)
 
TMS7-4007~ 
TMS7-40047 
TMS7-4030~ 
TMS7-4110 
TMS7-4132~ 
TMS7-4800 
110/460 
VAC 
995-00821-
00 
995-00823-
00 
995-00824-
00 
110/575 
VAC 
995-00825-
00 
995-00827-
00 
995-00828-
00 
 
 
Part Number 
Input 
Voltages 
(C45 
Models)
 
TMS7-4007~ 
TMS7-4022 
TMS7-4030~ 
TMS7-4110 
TMS7-4132~ 
TMS7-4800 
110/230 
VAC 
995-00829-
00 
995-00831-
00 
995-00832-
00 
 
6.3  Control Wiring 
 
TMS7 operation can be controlled using either the local push 
buttons, remote control inputs or the serial communications link. 
The <LOCAL/REMOTE> push button can be used to switch 
between local and remote control. Refer to Function 20. 
Local/Remote Operation for details. 
Remote Control Inputs 
The TMS7 has four remote control inputs. Contacts used for 
controlling these inputs should be low voltage, low current rated 
(Gold flash or similar). 
 
Remote push button control 
Reset
Stop
Start
I21
I22
I33
I34
I11
I12
I43
I44
FLC Select
 
Two wire control 
Reset
Stop
Start
I21
I22
I33
I34
I11
I12
I43
I44
FLC Select
 
 
CAUTION
 
CAUTION: 
Do not apply voltage to the control inputs. The 
inputs are active 24VDC and must be controlled 
with potential free circuits. 
Ensure contacts/switches operating the control 
inputs are suitable for low voltage, low current 
switching ie, gold flash or similar. 
Ensure cables to the control inputs are 
segregated from AC power and control wiring. 
 
Relay Outputs 
 
The TMS7 provides four relay outputs, one fixed and three 
programmable. Functionality of the programmable outputs is 
determined by the settings of Functions 21, 22 & 23. 
 
R23
R24
R33
R34
R43
R44
R12
R14
R11
* = default functionality
Functionality Assignmen
- Tripped
- Overcurrent trip
- Undercurrent trip
- Motor thermistor trip
- Starter overtemperature t
- Phase imbalance trip
- Electronic shearpin trip
- Low current alarm
- High current alarm
- Motor overload alarm
- Start/Run
- Main Contactor
Programmable
Output C
(*Tripped)
Run Output
Programmable Output B
(*Start/Run)
Programmable
Output A
(*Main Contactor)