CONTROL CIRCUITS 
 
14 
ME00070B 
TMS7 SERIES 
Start signal
Output voltage
RELAY FUNCTIONS
Main contactor
Start/Run
Run
Pre-start Tests
 
 
Motor Thermistors 
Motor thermistors (if installed in the motor) may be connected 
directly to the TMS7. A trip will occur when the resistance of the 
thermistor circuit exceeds approximately 2.8k
Ω
. The TMS7 can 
be reset once the thermistor circuit resistance falls below 
approximately 2.8k
Ω
 
 
Thermistor Input
C2
C1
No motor thermistors
C2
C1
Motor thermistors
Thermistor Input
 
 
CAUTION
 
NOTE: 
The thermistor circuit must be closed before the 
TMS7 will run. 
The thermistor circuit should be run in screened 
cable and must be electrically isolated from earth 
and all other power and control circuits. 
If no motor thermistors are connected to the TMS7 
thermistor input there must be a link across the 
thermistor input terminals C1 & C2. 
 
6.4  RS485 Serial Communication
 
 
The TMS7 has a non-isolated RS485 serial communication link. 
C5
C4
C3
RS485
GND
+
-
 
 
CAUTION
 
NOTE: 
Power cabling should be kept at least 300mm away 
from communications cabling. Where this cannot 
be avoided magnetic shielding should be provided 
to reduce induced common mode voltages. 
 
Data transmitted to and from the TMS7 must be in 8 bit ASCII, 
no parity, 1 stop bit. 
Baud rate is set by Function. 61 RS485 Baud Rate
The TMS7 can be programmed to trip if the RS485 link fails by 
setting Function 60. RS485 Timeout. 
The starter address is assigned using Function 62. RS485 
Satellite Address
The flow charts below show typical form of communication 
between an TMS7 and host controller. 
 
Host controller to TMS7 
START
SEND  TMS7
SLAVE ADDRESS
ACK
RECEIVED
TIMEOUT
N
N
Y
Y
D
C
DATA/
COMMAND
SEND  COMM AND
TIMEOUT
ACK
RECEIVED
Y
Y
N
N
N
Y
N
END
TIMEOUT
ERROR
LRC
ERROR
Y
N
Y
LRC
VALID
RECEIVE DATA
TIMEOUT
DATA
RECIEVED
SEND REQUEST
 
 
TMS7 to host controller 
N
Y
N
Y
N
N
Y
Y
N
Y
N
Y
Y
N
N
Y
N
Y
N
Y
N
Y
START
EOT
DETECT
RECEIVE
ADDRESS
ENQ
EOT
L RC
VALI D
ADDRESS
VALI D
SEND ACK
STX
EOT
RECEIVE DATA
ETX
EOT
L RC
VALI D
SEND NAK
SEND
DATA
CONTROL TMS7
SEND  DATA
SEND ACK
 
 
The following code sequences are used in the communications 
between the host and the TMS7 (network). 
 
Address slave unit. 
ASCII  EOT  [nn] 
LRC
 
ENQ 
or 
04h 
[n1]h [n2]h 
[LRC1]h [LRC2]h
 
05h 
 
Slave response. 
ASCII  ACK 
or 
06h