RO SYSTEM TROUBLE SHOOTING 
 
PROBLEM REMEDY 
General 
High Product Water TDS 
 
Membrane frozen, high temp, or backpressure. Replace 
membrane. 
Membrane attack by chlorine  
Carbon pre-filter may be exhausted. Replace filter and membrane. 
Product seal on end cap. 
Determine if seal or o-ring is bad. Replace as needed. 
No Product Water or Not Enough Product Water 
 
Feed water shut off. 
Turn on feed water. 
Low feed pressure. Feed pressure must be at least 10 psi. 
Consider booster pump. 
Pre-filter cartridge clogged. 
Replace pre-filter cartridge. 
Membrane fouled. 
Determine and correct cause; replace or clean  membrane. 
Product check valve stuck. 
Clean or replace check valve. 
Low pump discharge pressure 
Low feed water temperature 
Adjust reject valve or replace pump 
Increase membrane feed pressure or heat the feed water. 
 
 
 
 
 
IV. 
REPLACEMENT PARTS LIST 
 
 
A list of common replacement parts is provided below.  Contact your dealer for replacement 
parts assistance. 
 
Part Number 
Description 
FPMB5-978 Prefilter 
for 
R13-0250 
FPMB5-20 
Prefilter for R13-0600 & R13-1200 
R96310 
RO membrane for R13-0250 
R96320 
RO membrane for R13-0600 & R13-1200 
PG07B25 Prefilter 
pressure gauge 0 – 100 psi 
PG20B25 
Pump discharge pressure gauge 0 – 300 psi 
R5645 
Product and reject flow meter 0 – 50 gph 
WDM-2 Water 
quality 
meter 
R2200-120/60 
Motor 0.5 HP single phase 120 volt 
R2101-140 
Pump 140 GPH carbonator with relief valve 
R23-1070S 
Low pressure controller with on/off switch 
R23-PS32 Low pressure switch, ¼” MPT 
NV-10 
Reject & recycle needle valve 
R2402 
Inlet solenoid valve, 1/2”, 120 volt coil 
R9812-4SS 
Product check valve