Hoshizaki MRH/3 사용자 설명서

다운로드
페이지 94
48
4. Pump-Out Frequency Control (S4 dip switch 5 & 6)
NOTICE
Do not adjust on KM-515M_H without harvest pump timer. Adjustments to this setting 
on KM-515M_H without harvest pump timer may adversely affect performance and 
warranty coverage.
The pump-out frequency control is factory set to drain the water tank every 10 cycles 
on all KM-320M_H, KM-600MAH, KM-650M_H, KM-901M_H/3 and on KM-515MAH 
with harvest pump timer, and every cycle on KM-515M_H without harvest pump timer. 
Generally no adjustment is required. However, where water quality is bad and the 
icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The 
pump-out frequency control can be set to have a pump-out occur every cycle, or every 
2, 5, or 10 cycles. 
Timing of the first pump-out is dependent on the control board. On "E" control boards, the 
first pump-out is after the first freeze cycle. On "G" control boards, the first pump-out is 
dependent on S4 dip switch 5 & 6. See the table below.
"E" & "G" Control Board
1st Pump-Out
S4 Dip Switch Setting
Pump-Out 
Frequency
"E" Control Board
"G" Control Board
No. 5
No. 6
OFF
OFF
Every cycle
After 1st freeze cycle
After 2nd freeze cycle
ON
OFF
Every 2 cycles
After 3rd freeze cycle
OFF
ON
Every 5 cycles
After 6th freeze cycle
ON
ON
Every 10 cycles
After 11th freeze cycle
5. Bin Control Selector or Harvest Pump Timer Operation (S4 dip switch 7)
Depending on the control board, S4 dip switch 7 is used for either bin control selection or 
harvest pump timer operation.
(1) Bin Control Selector, "E" Control Board
NOTICE
Do not adjust. This dip switch must be left in the factory default position or the 
icemaker will not operate correctly.
When set to on position on an icemaker with a thermostatic bin control, a 5-beep alarm 
sounds (open circuit) and the icemaker does not operate.
"E" Control Board
S4 Dip Switch Setting
Bin Control
No. 7
ON
Mechanical (requires resistor wire harness)
OFF
Thermostatic