Toshiba 4200FA XT1 사용자 설명서

다운로드
페이지 10
 
4200FA XT1  
 
 
September 6, 2004
 
 
8
     See “System Diagnostics” for specific fault. 
 
3) SYSTEM METERING - The UPS shall be provided with a single read- 
out display which displays, upon request, the following information: 
 
AC INPUT VOLTAGE (Line to Line) 
 
 
 
AC OUTPUT VOLTAGE (Line to Line, Line to Neutral) 
   AC 
OUTPUT 
CURRENT 
   BATTERY 
VOLTAGE 
   BATTERY 
CHARGING 
CURRENT 
   INPUT 
FREQUENCY 
 
   OUTPUT 
FREQUENCY 
 
   INPUT/ 
OUTPUT 
kW 
   POWER 
FACTOR 
 
 
 
 
4) SYSTEM DIAGNOSTICS - The following diagnostic information shall be 
provided to troubleshoot the UPS should a fault occur: 
 
UPS Ok 
UPS Overload (including Bypass) 
Memory Error 
Inverter Output Current Limit 
Wrong Phase Rotation of AC Input  Low Battery Voltage 
Internal AC Circuit Fault 
I/O not Synchronized 
Internal DC Circuit Fault 
Auto-transfer Mode 
Heatsink Overheat 
Fuse Open 
DC unbalanced 
Battery Discharging Mode 
DC Circuit Over/Under voltage 
UPS Output Disabled 
DC Circuit Overcurrent 
 
Chopper Input Overcurrent 
 
Inverter Overcurrent 
 
Inverter Over/Under voltage 
 
Inverter Overload 
 
 
5.0 MECHANICAL DESIGN 
 
  A. 
UPS 
Enclosure 
 
The UPS shall be in a freestanding, NEMA1 enclosure equipped with  
casters and leveling feet.  The overall dimensions and weights shall be as  
follows (without internal batteries): 
 
 
  UPS 
Size 
  Dimensions   
 
 
Weight 
 
 
50 kVA  
 
35.60”W x 37.6”D x 59.8”H  
     1,581-1,946 lbs.