See “System Diagnostics” for specific fault.
3) SYSTEM METERING - The UPS shall be provided with a single read-
out display which displays, upon request, the following information:
out display which displays, upon request, the following information:
AC INPUT VOLTAGE (Line to Line)
AC OUTPUT VOLTAGE (Line to Line, Line to Neutral)
AC
OUTPUT
CURRENT
BATTERY
VOLTAGE
BATTERY
CHARGING
CURRENT
INPUT
FREQUENCY
OUTPUT
FREQUENCY
INPUT/
OUTPUT
kW
POWER
FACTOR
4) SYSTEM DIAGNOSTICS - The following diagnostic information shall be
provided to troubleshoot the UPS should a fault occur:
provided to troubleshoot the UPS should a fault occur:
UPS Ok
UPS Overload (including Bypass)
Memory Error
Inverter Output Current Limit
Wrong Phase Rotation of AC Input Low Battery Voltage
Internal AC Circuit Fault
Internal AC Circuit Fault
I/O not Synchronized
Internal DC Circuit Fault
Auto-transfer Mode
Heatsink Overheat
Fuse Open
DC unbalanced
Battery Discharging Mode
DC Circuit Over/Under voltage
UPS Output Disabled
DC Circuit Overcurrent
Chopper Input Overcurrent
Inverter Overcurrent
Inverter Over/Under voltage
Inverter Overload
5.0 MECHANICAL DESIGN
A.
A.
UPS
Enclosure
The UPS shall be in a freestanding, NEMA1 enclosure equipped with
casters and leveling feet. The overall dimensions and weights shall be as
follows (without internal batteries):
UPS
Size
Dimensions
Weight
50 kVA
35.60”W x 37.6”D x 59.8”H
1,581-1,946 lbs.
.