“F” Group: Main Profile Parameters
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–8
“F” Group: Main Profile Parameters
The basic frequency (speed) profile is 
defined by parameters contained in the “F” 
Group as shown to the right. The set 
running frequency is in Hz, but accelera-
tion and deceleration are specified in the 
time duration of the ramp (from zero to 
maximum frequency, or from maximum 
frequency to zero). The motor direction 
parameter determines whether the keypad 
Run key produces a FWD or REV command. This parameter does not affect the intelli-
gent terminal [FWD] and [REV] functions, which you configure separately.
Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the 
main profile. Accel and decel values for an alternative profile are specified by using 
parameters A_92 through A_93. The motor direction selection (F_04) determines the 
direction of rotation as commanded only from the keypad.
Output 
frequency
F 01
F 02
F 03
t
0
“F” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE 
(CE)
–FU 
(UL)
–FR 
(Jpn)
Units
F_01
Output frequency 
setting
Standard default target 
frequency that determines 
constant motor speed,
range is 0 to 360 Hz
0.0
0.0
0.0
Hz
TM 000.0   0.0Hz
F_02
Acceleration 1 time 
setting
Standard default acceleration,
range is 0.1 to 3000 sec.
10.0
10.0
10.0
sec.
ACC 1    0010.0s
F_03
Deceleration 1 time 
setting
Standard default deceleration,
range is 0.1 to 3000 sec.
10.0
10.0
10.0
sec.
DEC 1    0010.0s
F_04
Keypad Run key 
routing
Two options; select codes:
00... Forward
01... Reverse
00
00
00
INIT DOPE    FWD