“A” Group: Standard Functions
Basic Parameter Settings
These settings affect the most fundamental behavior of the inverter—the outputs to the 
motor. The frequency of the inverter’s AC output determines the motor speed. You may 
select from three different sources for the reference speed. During application develop-
ment you may prefer using the potentiometer, but you may switch to an external source 
(control terminal setting) in the finished application, for example.
The base frequency and maximum frequency settings interact according to the graph 
below (left). The inverter output operation follows the constant V/f curve until it reaches 
the full-scale output voltage. This initial straight line is the constant-torque part of the 
operating characteristic. The horizontal line over to the maximum frequency serves to let 
the motor run faster, but at a reduced torque. If you want the motor to output constant 
torque over its entire operating range (limited to the motor nameplate voltage and 
frequency rating), then set the base frequency and maximum frequency equal as shown 
(below right).
Base
 Frequency
Maximum
 Frequency
Base frequency = 
maximum frequency
A 03
A 04
A 03
A 04
V
V
100%
100%
f
f
Constant torque
0
0
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE 
(CE)
–FU 
(UL)
–FR 
(Jpn)
Units
A_01 Frequency source 
setting
 Three options; select codes:
00 ...Keypad potentiometer
01 ...Control terminal
02 ...Function F01 setting
01
01
00
F-SET-SELECT TRM
A_02 Run command source 
setting
Two options; select codes:
01 ...Control terminal
02 ...Run key on keypad, or
         digital operator
01
01
02
F/R SELECT TRM
A_03 Base frequency setting
Settable from 50 Hz to the 
maximum frequency
50.0
60.0
60.0
Hz
F-BASE     060Hz
A_04 Maximum frequency 
setting
Settable from the base 
frequency up to 360 Hz
50.0
60.0
60.0
Hz
F-MAX      060Hz