DC Braking Settings
The DC braking feature can provide 
additional stopping torque when 
compared to a normal deceleration to a 
stop. DC braking is particularly useful 
at low speeds when normal decelera-
tion torque is minimal. When you 
enable DC braking, the inverter injects 
a DC voltage into the motor windings 
during deceleration below a frequency you can specify (A_52). The braking power 
(A_54) and duration (A_55) can both be set. You can optionally specify a wait time 
before DC braking (A_53), during which the motor will free run (coast).
CAUTION: Be careful to avoid specifying a braking time that is long enough to cause 
motor overheating. If you use DC braking, we recommend using a motor with a built-in 
thermistor, and wiring it to the inverter’s thermistor input (see 
). Also refer to the motor manufacturer’s specifications for 
duty-cycle recommendations during DC braking.
DC braking
Free run
Running
A 53
A 55
t
0
+
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE 
(CE)
–FU 
(UL)
–FR 
(Jpn)
Units
A_51 DC braking enable
Two options; select codes:
00 ...Disable
01 ...Enable
00
00
00
DCB SW       OFF
A_52 DC braking frequency 
setting
The frequency at which DC 
braking occurs,
range is 0.5 to 10 Hz
0.5
0.5
0.5
Hz
DCB F     00.5Hz
A_53 DC braking wait time
The delay from the end of Run 
command to start of DC 
braking (motor free runs until 
DC braking begins)
0.0
0.0
0.0
sec.
DCB WAIT    0.0s
A_54 DC braking during 
deceleration
Applied level of DC braking 
force, settable from 0 to 100% 
0
0
0
%
DCB V        000
A_55 DC braking time for 
deceleration
Sets the duration for DC 
braking, range is 0.1 to 60.0 
seconds
0.0
0.0
0.0
sec.
DCB T      00.0s