“A” Group: Standard Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–16
Frequency-related Functions
Frequency Limits – Upper and lower 
limits can be imposed on the inverter 
output frequency. These limits will apply 
regardless of the source of the speed refer-
ence. You can configure the lower 
frequency limit to be greater than zero as 
shown in the graph to the right. The upper 
limit must not exceed the rating of the 
motor or capability of the machinery.
Upper
limit
Frequency command
Lower
limit
Settable
range
A 61
A 62
Output
frequency
0
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE 
(CE)
–FU 
(UL)
–FR 
(Jpn)
Units
A_61 Frequency upper limit 
setting
Sets a limit on output 
frequency less than the 
maximum frequency (A_04) 
Range is 0.5 to 360.0 Hz
0.0 ..setting is disabled
>0.1 setting is enabled
0.0
0.0
0.0
Hz
LIMIT H  000.0Hz
A_62 Frequency lower limit 
setting
Sets a limit on output 
frequency greater than zero 
Range is 0.5 to 360.0 Hz
0.0 ..setting is disabled
>0.1 setting is enabled
0.0
0.0
0.0
Hz
LIMIT L  000.0Hz