“A” Group: Standard Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–18
PID Control
When enabled, the built-in PID loop calculates an ideal inverter output value to cause a 
loop feedback process variable (PV) to move closer in value to the setpoint (SP). The 
current frequency command serves as the SP. The PID loop algorithm will read the 
analog input for the process variable (you specify the current or voltage input) and calcu-
late the output.
• A scale factor in A_75 lets you multiply the PV by a factor, converting it into 
engineering units for the process.
• Proportional, integral, and derivative gains are all adjustable.
• See 
 for more information.
NOTE: The setting A_73 for the integrator is the integrator’s time constant Ti, not the 
gain. The integrator gain Ki = 1/Ti. When you set A_73 = 0, the integrator is disabled.
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE 
(CE)
–FU 
(UL)
–FR 
(Jpn)
Units
A_71 PID Enable
Enables PID function,
two option codes:
00 ...PID Disable
01 ...PID Enable
00
00
00
PID SW       OFF
A_72 PID proportional gain
Proportional gain has a range 
of 0.2 to 5.0
1.0
1.0
1.0
PID P        1.0
A_73 PID integral time 
constant
Integral time constant has a 
range of 0.0 to 150 seconds
1.0
1.0
1.0
sec.
PID I     001.0s
A_74 PID derivative time 
constant
Derivative time constant has a 
range of 0.0 to 100 seconds
0.0
0.0
0.0
sec.
PID D       00.0
A_75 PV scale conversion
Process Variable (PV) scale 
factor (multiplier), range of
0.01 to 99.99
1.00
1.00
1.00
PID CONV   01.00
A_76 PV source setting
Selects source of Process 
Variable (PV), option codes:
00 ...[OI] terminal (current in)
01 ...[O] terminal (voltage in)
00
00
00
PID INPT     CUR