The table below lists the performance of 200V-class inverter models with the optional external
braking units. In some cases, the resistor selection specifies multiple resistors in a parallel,
series, or combination parallel/series configuration. The example diagram shows a parallel
configuration. Please refer to the braking resistor documentation for detailed wiring diagrams.
braking units. In some cases, the resistor selection specifies multiple resistors in a parallel,
series, or combination parallel/series configuration. The example diagram shows a parallel
configuration. Please refer to the braking resistor documentation for detailed wiring diagrams.
200V Class
Braking Unit
Dynamic Braking Resistor Selection
Max.
Braking
Torque,
%
Model Number
SJ300
Type
Type
x (quantity)
Series or
Parallel
Total
Ohms
Total
Watts
Max.
Duty
Cycle,
%
–150LFU
BRD–E2
HRB1
—
50
400
10
30
HRB2
—
35
600
10
35
HRB3
—
17
1200
10
60
BRD–E2–30K
HRB3 x (2)
parallel
8.5
2400
20
110
HRB3 x (3)
parallel
5.7
3600
20
150
HRB3 x (4)
parallel
4.3
4800
20
200
–185LFU
BRD–E2
HRB1
—
50
400
10
25
HRB2
—
35
600
10
30
HRB3
—
17
1200
10
50
BRD–E2–30K
HRB3 x (2)
parallel
8.5
2400
20
90
HRB3 x (3)
parallel
5.7
3600
20
130
HRB3 x (4)
parallel
4.3
4800
20
170
–220LFU
BRD–E2
HRB1
—
50
400
10
25
HRB2
—
35
600
10
30
HRB3
—
17
1200
10
45
BRD–E2–30K
HRB3 x (2)
parallel
8.5
2400
20
80
HRB3 x (3)
parallel
5.7
3600
20
110
HRB3 x (4)
parallel
4.3
4800
20
150
–300LFU
BRD–E2–30K
HRB3 x (2)
parallel
8.5
2400
20
55
HRB3 x (3)
parallel
5.7
3600
20
80
HRB3 x (4)
parallel
4.3
4800
20
110
–370LFU
BRD–E2–30K
HRB3 x (2)
parallel
8.5
2400
20
45
HRB3 x (3)
parallel
5.7
3600
20
65
HRB3 x (4)
parallel
4.3
4800
20
90
–450LFU
BRD–E2–30K
HRB3 x (2)
parallel
8.5
2400
20
35
HRB3 x (3)
parallel
5.7
3600
20
50
HRB3 x (4)
parallel
4.3
4800
20
75
Braking
Unit
Inverter
Example configuration
HRB3 x (4) parallel