Bosch d9412gv3 사용자 설명서
D9412GV3/D7412GV3 | Operation and Installation Guide | 3.0
Overview
.
Bosch Security Systems, Inc. | 10/10 | F01U143070-03
9
3.0 Overview
3.1
Configuration and Parts
Figure 1: System Configuration
Control
Panel
On-Board Points
1 to 8
D9131A Module connects
to a parallel printer to print
the event log.
D928 Module allows the control
panel to monitor two phone lines.
Each D8128D OctoPOPIT combines
eight POPIT points in one module.
D8132 Modules (two 12 VDC batteries)
provide additional power for keypads and
other powered devices.
D8129 OctoRelay provides alarm
and auxiliary relay output.
(Other functions available.)
D9210B Modules can be
used for access control.
Use keypads or keyswitches to arm the control panel by
area. The D9412GV3 control panel supports up to 32 areas.
The D7412GV3 control panel supports up to 8 areas. Each
area can have its own account number or areas can be
grouped together with a common account number. Points of
protection are assigned to areas.
D8125, ISW-D8125CW-V2 or D8125MUX
Interface used for point expansion.
DX4020 or ITS-DX4020-G allows
communciation over a Local or Wide
Area Network (LAN/WAN).
Table 2:
GV3 Series Control Panel Differences
Features
D9412GV3
D7412GV3
D7212GV3
Access Control
Yes - 8 doors
Yes - 2 doors
No
Arm/Disarm Passcodes
249
99
99
Cards/Tokens
996
396
N/A
Passcode-Protected Custom Functions
16
4
4
Number of Printers
3
1
1
Number of Points
246
75
40
Number of Relays
128
64
24
Number of Areas
32
8
4
Number of D1255 Keypads
16
16
8
Number of D1260 Keypads
8
8
8