required if the room is cool (<75°F).  For higher rack mounting densities, forced-air rack 
ventilation is strongly recommended.  Please note the average per-unit power dissipation of 45 
watts (@ max LNB DC current loading) and plan accordingly. 
Table 1.  Equipment Specifications 
Parameter Specification 
Input Rating 
115/230 VAC, 0.8/0.5A, 50/60Hz 
Operating Temperature Range 
5° - 40° C 
Operating Humidity 
Maximum relative humidity 80% for 
temperatures up to 31° C, decreasing linearly 
to 50% relative humidity at 40° C. 
Maximum Operating Elevation  
6560 Ft (2000M) above sea level 
 
1.3.3 Elevated 
Operating 
Ambient 
If equipment is installed in a closed or multi-unit rack assembly, the operating ambient of the 
rack may be greater than the room ambient.  Therefore, considerations should be given to the 
TMRA, or Temperature inside the Mounting Rack, and not just inside the room. 
1.3.4 
Reduced Air Flow 
Installation of the equipment in a rack should be such that the amount of airflow required for safe 
operation of the equipment is not compromised. 
1.3.5 Mechanical 
Loading 
Mounting of equipment in a rack should be such that a hazardous condition is not achieved due 
to uneven loading 
1.3.6 Circuit 
Overloading 
Consideration should be given to connection of the equipment to the supply circuit and the effect 
that overloading of circuits could have on overcurrent protection and supply wiring.  Appropriate 
consideration of equipment nameplate ratings should be used when addressing this concern. 
1.3.7 Reliable 
Earthing 
Reliable earthing of rack-mounted equipment should be maintained.  Particular attention should 
be given to supply connections other than direct connection to the Branch (use of power strips).