Chapter 5 - Point Commander 
Point Commander Application Overview 
38 
Siemens Industry, Inc. 
 
125-3584T
 
 
  
  The Relinquish Default field displays the default value for relinquishing priority of 
the point. 
  The Present Value field shows the present value of the point at the current highest 
priority, and allows you to change that value.  
  The Priority dropdown shows the current priority, and allows you to change the 
priority. Priorities 1 through 7 are not accessible; if they are chosen, the priority will 
automatically default to the highest accessible priority value. 
Command Feedback 
A successful command will initiate an automatic refresh of the point values. The 
Feedback field at the bottom left of the window displays a message indicating the 
success or failure of each action. If the command was not successful an error message 
displays, giving the reason for the failure. See the following table for a list of error 
messages. 
 
Error Code 
Situation 
UNKNOWN_OBJECT 
Specified object does not exist. 
UNKNOWN_PROPERTY 
Specified property does not exist. 
PROPERTY_IS_NOT_AN_ARRAY 
An array index is provided but the property is not 
an array.  
INVALID_ARRAY_INDEX 
An array index is provided that is outside the 
range existing in the property. 
WRITE_ACCESS_DENIED 
The specified property is currently read-only.