Chapter 5 - Point Commander 
  
Using the Point Commander Application
39
Siemens Industry, Inc. 
 
125-3584T
 
 
Error Code 
Situation 
INVALID_DATATYPE 
The data type of the value provided is incorrect 
for the specified property. 
VALUE_OUT_OF_RANGE 
The value provided is outside the range of values 
that the property can take on. 
NO_SPACE_TO_WRITE_PROPERTY 
There is not enough space to store the new 
value. 
DATATYPE_NOT_SUPPORTED 
The data being written has a data type not 
supported by the property. 
 
 
 
 
Tips for Using the Point Commander Application 
  Points can be commanded from the Navigation pane or from an animated graphic. 
See the 
FINlite Graphics Tool 
section for information on commanding a point from 
a graphic. 
  You can only command points if you have been given Command or higher access 
level to the point. 
–  Both analog and digital points can be commanded. 
–  Generally, only output points (AO, BO, and MSO) or virtual points (AV, BV, 
MSV) can be commanded; however, AI and BI input points can be commanded 
if taken out of service first. 
  If the same point is commanded from two different sessions, the command with the 
higher priority will override. If the commands are made with the same priority, the 
last command will override the earlier command.  
  Multi State Input Object (MSI) points are not supported on the FLN. 
  Use caution when moving the Commander window around the screen. If you move 
it too far up the screen, you may not be able to access the title bar and move the 
screen back down into view. 
Using the Point Commander Application 
 
Commanding Point Values 
Commanding a point means using the Point Commander Application to manually 
override the system program instructions for either an output point or a virtual input 
point. Point commanding changes the command priority from NONE. 
 
This procedure is only available to users with Command or higher access to points.