Siemens 125-3584T 사용자 설명서

다운로드
페이지 177
Chapter 5 - Point Commander 
  
Using the Point Commander Application
41
Siemens Industry, Inc. 
 
125-3584T
 
 
2.  Drill down to the desired point.  
3.  Double-click the point name (or single click the command icon to the right of the 
point name) to open the basic (default) Commanding window. 
4.  In the Command Options section do one of the following: 
-  To disable the point, check the Disabled check box and click Command. 
-  To re-enable the point, clear the Disabled check box and click Command. 
  The status of the command displays in the Command Status section. 
5.  Click Command to initiate the changes and begin controlling the point with the new 
settings.  
NOTE: If the point value is being changed as well, it is not necessary to check or 
uncheck the Out-of-Service check box in a separate step. 
  The status of the command displays in the Feedback field. 
This procedure is now complete. Close the Commander window by using the X in the 
top right corner of the window. 
 
Priority Arrays 
The Point Commander Application allows you to change the priority for commandable 
points. For more information about point priority, see the TALON Controllers User's 
Manual (588-580). 
Point priority can be changed via the basic or advanced Commanding window. Toggle 
between the Basic and Advanced command options using the Advanced/Basic button 
at the bottom of the Commander window.  
In the basic Commanding window, you can command the point to a new value and can 
change only one priority, but in the advanced Commanding window, you can populate 
the entire priority array with values.  
 
This procedure is only available to users with Command or higher access to points.
Steps for Changing Point Priority (Basic Commanding Window) 
In the basic Commanding window, the “At” field (@) displays the current priority and 
allows you to change the point priority.  
1.  Use the drop-down arrow to change the priority.  
2.  Click Command to initiate the change. The status of the command displays in the 
Feedback field. 
  The point value displays in the “At” field (@) as well as inthe current highest 
priority field in the advanced Commanding window. 
Steps for Changing Point Priority (Advanced Commanding Window)