Panasonic MINAS A5 사용자 설명서

다운로드
페이지 478
2-4
Installation Environment
Use the servo driver in the environment of Pollution Degree 1 or 2 prescribed in 
IEC-60664-1 (e.g. Install the driver in control panel with IP54 protection structure.)
*3
Metallic control box
100V/200V
Controller
Insulated power supply
for interface
Power 
supply
Circuit 
breaker
Residual
current device
(RCD) 
Surge 
absorber
Noise filter
Noise filter for signal lines
 *1
*1 A to D-frame: Noise filter for signal lines, E to H-frame: Noise filter for signal lines <Power supply cable>
*2 A to F-frame: Noise filter for signal lines, G, H-frame: Noise filter for signal lines <Motor cable>
*3 Only for position control type is not provided with X3 terminal.
Noise filter for 
signal lines
Noise filter for 
signal lines
Ground (PE)
L1
U
X4
XA
XB
X6
M
RE
V
W
L2
L3
L1C
L2C
Noise filter for 
signal lines
 *2
Driver
Motor
A to F-frame:
Motor cable
without shield
cable
G, H-frame:
Motor cable
with shield
cable
Safety
controller
X3
400V
*1 D to F-frame: Noise filter for signal lines, G, H-frame: Noise filter for signal lines <Power supply cable>
*2 D to F-frame: Noise filter for signal lines, G, H-frame: Noise filter for signal lines <Motor cable>
*3 Only for position control type is not provided with X3 terminal.
Insulated
DC24V
*3
Metallic control box
Controller
Insulated power supply
for interface
Power 
supply
Circuit 
breaker
Residual
current device
(RCD) 
Surge 
absorber
Noise filter
Noise filter for signal lines
 *1
Noise filter for 
signal lines
Noise filter for 
signal lines
Noise filter for 
signal lines
Ground (PE)
L1
U
X4
XA
XB
X6
M
RE
V
W
L2
L3
24V
0V
Noise filter for 
signal lines
 *2
Driver
Motor
Noise filter for 
signal lines
D to F-frame:
Motor cable
without shield
cable
G, H-frame:
Motor cable
with shield
cable
Safety
controller
X3
1. Conformance to international standards
EC Directives
‡0DQGDWRU\UHTXLUHPHQWVWRFRQIRUPWR(0&GLUHFWLYH
・ Install the servo driver on the metallic casing (control board).
・,QVWDOOQRLVHÀOWHUDQGOLJKWQLQJVXUJHDEVRUEHULQWKHSRZHUVXSSO\OLQH
・ Use braided shield cable (tin plated annealed copper wire) for I/O signal cable and 
encoder cable.
・3URYLGH WKH QRLVH ÀOWHU DV VKRZQ LQ WKH ÀJXUH IRU HDFK FDEOH ,2 OLQH DQG SRZHU
source line to be connected to the servo driver.
・6KLHOGRIFDEOHVQRWVKRZQRQWKHÀJXUHVKRXOGEHGLUHFWO\JURXQGHGWKURXJK3(
Because these conditions for EMC directive are affected by status of connected de-
vices, wiring, connection and location, compliance should be checked after completing 