SIMATIC PCS 7 TeleControl system components
12
PCS 7 TeleControl engineering station
Engineering station of the SIMATIC PCS 7 process control system
To enable engineering of the PCS 7 TeleControl operator sta-
tion (single station/server), the functions of the engineering 
station of the SIMATIC PCS 7 process control system are ex-
panded by DBA technology (Data Base Automation) and the 
SIMATIC PCS 7 TeleControl block library. 
Data Base Automation (DBA)
Engineering can be automated efficiently and in conformance 
with SIMATIC PCS 7 using the DBA technology. DBA supports 
plant expansion during ongoing operation, and facilitates 
project-specific adaptation of the system as well as importing 
of existing configurations in the course of migration.
The DBA executed in the engineering station automatically 
generates the OS runtime database with the display hierarchy, 
required variables, alarms, alarm messages and alarm priori-
ties, as well as the specific faceplates and block symbols. 
The display hierarchy is the basis for navigation between the 
process displays, for alarm management, and for implementa-
tion of safety measures. DBA positions the type-specific block 
symbols, e.g. measured value, counter value, motor or gate 
valve, in the process images. These symbols are linked to the 
corresponding function blocks and faceplates through the da-
tabase. Manual configuration is mainly limited to the design 
and positioning of the static graphic elements, e.g. pipes or 
tanks.
SIMATIC PCS 7 TeleControl block library
In addition to the SIMATIC PCS 7 TeleControl basic library, 
new user blocks can also be defined using the DBA type editor. 
During database generation, the user blocks are treated like 
the blocks from the basic library. 
Using the DBA type editor it is possible to assign the frequently 
unstructured variables of an RTU once to a block type and to 
display the variable structured on the operator station via the 
block's faceplate. 
SIMATIC PCS 7 TeleControl blocks
The PCS 7 TeleControl OS symbols, faceplates and diagnostics 
displays created in conformance with SIMATIC PCS 7 take into 
account the specific features of telecontrol applications. This 
is demonstrated, for example, by the example of the counter 
block which offers versatile conditioning options for informa-
tion on transported or processed quantities. At least one 
OS faceplate and one OS symbol are available for each type 
of block.
In addition to arrangement of information in a variable struc-
ture, the user blocks generated with the DBA type editor can 
also calculate derived values using Visual Basic scripts in the 
server. This results in numerous possibilities for extending the 
functionality and for adapting the system to individual cus-
tomer requirements. 
Type-specific OS faceplates and OS symbols for the user blocks 
can be created using the standard tools for SIMATIC PCS 7 
OS engineering (Graphics Designer and Faceplate Designer). 
© Siemens AG 2011