Siemens SIMATICS PCS7 사용자 설명서

다운로드
페이지 32
SIMATIC PCS 7 TeleControl system components
13
Remote terminal units
The remote control units supported by SIMATIC PCS 7 
TeleControl have a performance classified as Small, Medium 
or Large.
Controllers of SIPLUS extreme design are also available in all 
performance classes, and can be operated under extreme con-
ditions, e.g. ambient temperatures from -25 °C to +70 °C, con-
densation or exposure to media.
In addition, the SIMATIC S7-300F and S7-400F controllers can 
be used to implement safety-related applications on site and 
automatically set the plant to a safe status in the event of a 
dangerous fault. 
Classification of the remote terminal units
RTU
Applications
Possible tele-
control protocols
Information points/ 
buffer size
RTU Small: controller integrated in SIMATIC ET 200S
RTU with up to approx. 30 I/Os 
For small, cost-sensitive applica-
tions
• Modbus
No buffering
• IEC 870-5-101
• IEC 870-5-104
Up to approx. 200 information 
points
Buffer size: 
800 information points
RTU Medium: SIMATIC S7-300/S7-300F controller
RTU with up to approx. 100 I/Os
For medium-sized applications; 
extremely flexible configuration
S7-300F for safety-related appli-
cations
• SINAUT  ST7
• DNP3
TIM buffering 
(up to 16 000 frames or up to 
32 000 frames with TIM 3V-IE 
Advanced)
• Modbus
No buffering
• IEC 870-5-101
• IEC 870-5-104
Up to approx. 2 000 informa-
tion points 
Buffer size:  800 to 3 200 infor-
mation points
RTU Large: SIMATIC S7-400/S7-400F controller
RTU with up to approx. 500 I/Os 
For larger applications requiring 
increased performance
S7-400F for safety-related appli-
cations
• SINAUT  ST7
• DNP3
TIM buffering 
(up to 56 000 frames)
• Modbus
No buffering
• IEC 870-5-101
• IEC 870-5-104
Up to approx. 5 000 informa-
tion points
Buffer size: 3 200 information 
points
RTU Large: SIMATIC S7-400H/S7-400FH controller
Like S7-400/S7-400F
• DNP3
TIM buffering 
(up to 56 000 frames)
• IEC 870-5-101
• IEC 870-5-104
Up to approx. 5 000 informa-
tion points
Buffer size: 3 200 information 
points
© Siemens AG 2011