1.  Shut off unit, including pilot. Allow unit to 
cool for at least thirty minutes.
2.  Inspect burner, pilot and primary air inlet 
holes on injector holder for dust and dirt 
(see Figure 28).
3.  Blow air through the ports/slots and holes 
in the burner.
4.  Check the injector holder located at the 
end of the burner tube again. Remove 
any large particles of dust, dirt, lint or pet 
hair with a soft cloth or vacuum cleaner 
nozzle.
5.  Blow air into the primary air holes on the 
injector holder.
6.  In case any large clumps of dust have now 
been pushed into the burner repeat steps 
3 and 4.
Clean pilot assembly also. A yellow tip on the 
pilot flame indicates dust and dirt in the pilot 
assembly. There is a small pilot air inlet hole 
about 2" from where the pilot flame comes out 
of the pilot assembly (see Figure 29). With the 
unit off, lightly blow air through the air inlet 
hole. You may blow through a drinking straw 
if compressed air is not available.
CLEANING AND MAINTENANCE
Continued
Figure 28 - Injector Holder On Outlet 
Burner Tube
Burner Tube
Primary Air 
Inlet Holes
Injector Holder 
Figure 29 - Pilot Inlet Air Hole
Burner Tube
Pilot Assembly
Pilot Air 
Inlet Hole
Ports/Slots
LOGS
•  If  you  remove  logs  for  cleaning,  refer  to 
Installing Logs, page 16, to properly replace 
logs.
•  Replace log(s) if broken or chipped (dime-
sized or larger).
MAIN BURNER
Periodically inspect all burner flame holes with 
the heater running. All slotted burner flame 
holes should be open with yellow flame pres-
ent. All round burner flame holes should be 
open with a small blue flame present. Some 
burner flame holes may become blocked by 
debris or rust, with no flame present. If so, 
turn off heater and let cool. Remove blockage. 
Blocked burner flame holes will create soot.
SERVICE HINTS
When Gas Pressure Is Too Low
•  pilot will not stay lit
•  burners will have delayed ignition
•  heater will not produce specified heat
•  for propane/LP units, propane/LP gas sup-
ply may be low
You may feel your gas pressure is too low. If 
so, contact your local propane/LP or natural 
gas supplier.
TECHNICAL SERVICE
You  may  have  further  questions  about 
installation,  operation,  or  troubleshooting. 
If  so,  contact  FMI  PRODUCTS,  LLC  at 
1-866-328-4537. When calling please have 
your model and serial numbers of your 
heater ready.
You  can  also  visit  FMI  PRODUCTS,  LLC’s 
web site at 
www.fmiproducts.com.