Example: Space size 20 ft. (length) x 16 ft. 
(width) x 8 ft. (ceiling height) = 2,560 cu. ft. 
(volume of space)
 
If additional ventilation to adjoining room 
is supplied with grills or openings, add the 
volume of these rooms to the total volume 
of the space.
2.  Multiply the space volume by 20 to determine 
the maximum Btu/Hr the space can support.
 
 ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
 
Example: 2,560 cu. ft. (volume of space) x 
20 = 51,200 (maximum Btu/Hr the space can 
support)
3.  Add the Btu/Hr of all fuel burning appliances 
in the space.
 
Vent-free fireplace 
 __________ Btu/Hr
 
Gas water heater* 
 __________ Btu/Hr
 
Gas furnace 
 __________ Btu/Hr
 
Vented gas heater 
 __________ Btu/Hr
 
Gas fireplace logs 
 __________ Btu/Hr
 
Other gas appliances* + _________ Btu/Hr
 Total 
= _________ Btu/Hr
 
* Do not include direct-vent gas appliances. 
Direct-vent draws combustion air from the 
outdoors and vents to the outdoors.
 
Example:
 
Gas water heater 
 __________ Btu/Hr
 
Vent-free fireplace 
+ _________ Btu/Hr
 Total 
= _________ Btu/Hr
4.  Compare the maximum Btu/Hr the space can 
support with the actual amount of Btu/Hr used.
 
 _______ Btu/Hr (maximum the space can 
support) 
 
 _______ Btu/Hr (actual amount used)
 
Example:  51,200  Btu/Hr  (maximum  the 
space can support)
 
 
79,000 Btu/Hr (actual amount of 
Btu/Hr used)
The space in the example is a confined space 
because the actual Btu/Hr used is more than the 
maximum  Btu/Hr  the  space  can  support. You 
must provide additional fresh air. Your options 
are as follows:
A.  Rework worksheet, adding the space of an 
adjoining room. If the extra space provides an 
unconfined space, remove door to adjoining 
room or add ventilation grills between rooms. 
See Ventilation Air From Inside Building.
B.  Vent room directly to the outdoors. See 
Ventilation Air From Outdoors
, page 8
.
C.  Install a lower Btu/Hr fireplace, if lower Btu/
Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support,
 the space is 
an unconfined space. You will need no additional 
fresh air ventilation.
 WARNING: If the area in which 
the heater may be operated does 
not meet the required volume for 
indoor combustion air, combus-
tion and ventilation air shall be 
provided by one of the methods 
described in the National Fuel 
Gas Code, ANSI Z223.1/NFPA 54, 
the International Fuel Gas Code, 
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining 
unconfined  space.  When  ventilating  to  an 
adjoining unconfined space, you must provide 
two permanent openings: one within 12" of the 
ceiling and one within 12" of the floor on the 
wall connecting the two spaces (see options 
1 and 2, Figure 2). You can also remove door 
into adjoining room (see option 3, Figure 2). 
Follow  the  National Fuel Gas Code, ANSI 
Z223.1/NFPA 54, Air for Combustion and 
Ventilation  for  required  size  of  ventilation 
grills or ducts.
AIR FOR COMBUSTION AND VENTILATION
Continued
  40,000
  39,000
  79,000
Figure 2 - Ventilation Air from Inside 
Building
Or 
Remove 
Door into 
Adjoining 
Room, 
Option 
Ventilation Grills  
Into Adjoining Room, 
Option 2 
Ventilation
Grills Into
Adjoining 
Room,
Option 1
12" 
12"