Trouble Shooting
Problem
Possible Cause
Solution
Spark will not light the 
pilot after repeatedly 
pressing the spark ignitor
Defective piezo ignitor.
• Check connections to ignitor.
• If ignitor connections are good but no spark, replace 
ignitor.
Broken spark electrode.
• Check for broken ceramic insulation, replace 
electrode if broken.
Low battery or bad 
electronic module.
• Replace the electronic module or replace the battery 
in module.
Misaligned spark electrode. • If spark is not arcing from electrode to pilot, loosen 
the screws on the pilot base adjust and tighten.
Pilot will not remain lit
Problem with thermocouple 
circuit
• Check for proper connection of the thermocouple to 
the rear of the valve. If loose, fully tighten lightly.
• Check pilot for full flame impingement around 
thermocouple.  If flame is too small, check gas 
pressure, adjust pilot rate screw, check pilot head for 
damage or blockage.
• Check thermocouple voltage at rear of valve. It must 
be greater than 7 mV.  If low, replace thermocouple.
Air in gas line (pilot dies 
while knob is depressed)
• Bleed line.
• Check gas line pressure.
• Contact dealer.
Burners will not remain 
lit
Problem with thermopile 
circuit
• Check gas line pressure .
• Check for flame impingement on thermopile. If low, 
see “Pilot will not remain lit”.
• Check thermopile for minimum of 200mV when 
burner is switched on.
• Check wiring to thermostat for breaks.
Flame lifting
Leak in vent pipe
• Check for leaks in vent connections.
Improper vent configuration • Check vent configuration with manual.
Terminal may be 
recirculating flue gases
• Check to see if terminal is on correctly.
• May need to install high wind termination cap.
• Contact dealer.
Improperly set vent 
restrictor plate.
• See venting section for proper restrictor setting.
Glass fogs up
Normal Condition: after the appliance warms up the glass will clear.
**Due to additives in gas, glass may get hazy during operation** Clean as needed.
Blue Flames
Normal during start up: flames will yellow as the fireplace heats up.
Flames are burning 
“dirty” or sooting
Flame impingement
• Check log positioning.
• Check vent restrictor for proper setting.
• See also “Burners will not remain lit.”