Enviro 50-1033 Manual Do Utilizador

Página de 48
27
Firebox Top
Flue Collar
Adapter
Undo four 1⁄4"
screws that
hold flue collar
elbow to unit.
Figure 40: Step 3 of Converting Top Vented into 
Rear Vented.
Figure 41: Step 4 of Converting Top 
Vented into Rear Vented.
I
NSTALLATION
 
OF
 R
EAR
 V
ENTED
 A
PPLIANCE
:
Siding
Exterior wall
Drywall
Vent pipe
Inside finished collar
Wall thimble
Minimum vent terminal 36"
(91.4cm) high snorkel kit.
Figure 42: Installation for Rear Vented; 
30,000 Btu/hr.
2. Remove the four (4) 1⁄4” screws that hold the flue collar elbow to the unit body (see Figure 40). 
3. Carefully remove the elbow being sure not to damage the gasket that is glued to the flue collar elbow, 
it seals the flue to the firebox.
4. Turn the elbow to the rear vent position and re-fasten with the screws removed in step 2 (see Figure 
41).
Place the unit into position.
Attach a small section of pipe on the unit and mark exterior wall 
where vent would pass through the wall.
Cut  a  10”  (25.4  cm)  minimum  hole  in  the  wall  to  maintain 
clearances to combustibles. Frame hole as shown in Figure 26.
Install a wall thimble.
Install interior finished collar.
Install the vent section through the wall.
THIS UNIT MUST BE VENTED WITH A 36” (91 cm) SNORKEL KIT 
IF UNIT IS RATED FOR 30,000 Btu/hr NG and 26,000 Btu/hr LP.
Seal  around  the  vent  terminal  to  the  structure  using  a  non 
hardening mastic.
Also refer to I
NITIAL
 I
NSTALLATION
 - V
ENT
 C
ONFIGURATIONS
 
AND
 R
ESTRICTOR
 
S
ETTINGS
.
Initial Installation
QUALIFIED INSTALLERS ONLY