Gas-Fired Products PTU Manual Do Utilizador

Página de 4
MODEL
PTS/U 40
40,000
40,000
25,000
PTS/U 50
50,000
50,000
30,000
PTS/U 75
75,000
75,000
50,000
PTS/U 100
100,000
100,000
65,000
MODEL SELECTIONS
GENERAL FEATURES
8 different Btu/hr sizes and more than 100
different configurations to custom design your
infrared heating system
Single Stage or Two Stage Input Controls
CSA design certified
Vented or indirect vented operation
Sidewall or through-the-roof venting
Natural and propane gas models
PUSH THROUGH SYSTEM
(Positive Pressure)
Products of combustion are pushed through the
combustion chamber
Tube Integrity Safety System (TISS)
No draft hoods, totally enclosed
combustion chamber
Blower motor totally enclosed in the burner box.
Ideal for applications where minimal noise (less
than 60dB) is desired
Heavy duty permanently lubricated, ball bearing
blower motor for maintenance-free operation
BURNER SYSTEM
Heavy-duty cast iron burner
10-year limited warranty on burner
Inside or outside air for combustion
Up to 40 ft. outside combustion air duct capability
Standard 4” combustion air collar
Reliable direct spark ignition system and 100%
gas shut-off safety control
Pre-purge and post-purge function
State-of-the-art step opening redundant
combination gas valve for quiet ignition and
added safety
Diaphragm air switch for proof of venting before
gas flow and ignition
Diagnostic monitoring light system
Burner inspection sight glass
Line voltage or 24V thermostat connection
RADIANT EMITTER TUBE SYSTEM
4” O.D. heavy-duty calorized aluminized steel or
alumi-therm steel combustion chamber (10 feet)
and heavy duty hot-rolled steel radiant emitter
tubes
Optional calorized aluminized steel (ALC)
radiant emitter tubes
3-year limited warranty on the emitter tubes
Suitable for horizontal or angle mounting up to 45°
Optional 90° elbows
Up to 40 feet sidewall vent capacity
REFLECTOR SYSTEM
Highly efficient aluminum reflectors with
reflectivity rating of 97.5%
Optional end, corner, side and U-bend reflectors
Optional decorative grille
Individual reflectors can be rotated up to 45° to
direct heat where needed
Easy-to-use mounting brackets and wire hangers
TOTAL EMITTER TUBE LENGTH*
10 FT**
20 FT
30 FT
40 FT
PTS/PTU SERIES FEATURES
GAS
TYPE
NATURAL
3.5” W.C.
5” W.C*
14” W.C.
PROPANE
10” W.C.
11” W.C.*
14” W.C.
BURNER
PRESSURE
VOLTAGE
AMPS
IGNITION
TYPE
MIN
MAX
120 VAC
60 HZ
1.8
DIRECT
SPARK
*Indicate model number based on Btu/hr input (e.g., 100,000 Btu/hr), total emitter length, (e.g., 40 feet) and gas type
(e.g., natural gas single stage input). The unit selection for a straight tube would be PTS100-40-N5 and for a U-tube
would be PTU100-40-N5. **Available only on PTS models.
ALC Option: All calorized aluminized steel (ALC) radiant emitter tubes
for ALC option the model number would be PTS100-40-ALC-N5. Note: for Carwashes, Dairy Barns, Greenhouses,
Swimming Pools, Waste Water Treatment Plants, and other high humidity / corrosive environments, the ALC option with
all calorized aluminized tubes is recommended.
SUPPLY PRESSURE
SINGLE
STAGE
BTU/HR
INPUT
FLUE
CONNECTION
OUTSIDE COMBUSTION
AIR CONNECTION
4” Round
4” Round
Btu/hr
High Input
Btu/hr
Low Input
TWO STAGE
X
X
X
X
X
X
X
X
MODEL
PTS/U 125
125,000
125,000
80,000
PTS/U 150
150,000
150,000
100,000
PTS/U 175
175,000
175,000
110,000
PTS/U 200
200,000
200,000
125,000
TOTAL EMITTER TUBE LENGTH*
30 FT
40 FT
50 FT
60 FT
70 FT
SINGLE
STAGE
BTU/HR
INPUT
Btu/hr
High Input
Btu/hr
Low Input
TWO STAGE
X
X
X
X
X
X
X
X
X
X
X
X
CONTROL SUFFIX
N5 / L5
N7 / L7
TYPE OF GAS
Natural / Propane
Natural / Propane
CONTROL OPTION DESCRIPTION
Single Stage Gas Valve - Single Stage Input
Two Stage Gas Valve - Two Stage Input - High/Low Fire
®
Energy efficient PTS150-40 installed in a manufactur-
ing application.