CONVERTING CLASS-A 
METAL CHIMNEY OR
 MASONRY  CHIMNEY 
TO DIRECT 
VENT SYSTEM
There are two different types of direct vent 
conversion systems listed below. Follow the 
appropriate directions for your installation.
A)  Through an existing factory built metal 
chimney going through the ceiling: A typical 
conversion of this type is shown in diagram 
1. The concept of direct vent conversion is 
to connect an adaptor to an Underwriters 
Laboratories (UL) listed 4 inch diameter 
aluminum fl ex pipe which is then passed 
down through the center of the existing metal 
chimney system. Three sizes of Top Adap-
tors are available from Simpson Dura-Vent. 
The Retro Connector (909B) is attached to 
the bottom of the fl ex pipe. The Top Adaptor 
and the Retro Connector are attached to the 
existing chimney with sheet metal screws. 
The appliance is then connected to the 
chimney with appropriate black direct vent 
pipe and an adjustable length  section.
B)  Through the wall of an existing masonry 
chimney: A typical conversion of an existing 
masonry chimney is shown in Diagram 6. A 
Top Adaptor (985K) and Flashing are used at 
the top of the masonry chimney. The 4 inch 
aluminum liner is connected to the adaptor 
and is passed down the chimney and out 
through the  masonry wall and attached 
to the Retro Connector (909B). The Retro 
Connector is attached to the masonry wall 
and then connected to the direct vent pipe 
leading to the appliance.
Prior to installation and connection of the 
vent system to a factory-built or masonry 
chimney, the chimney must be inspected and 
thoroughly cleaned by a qualifi ed  service 
person, such as a certifi ed chimney sweep 
or home inspection service.
The direct vent system must not be con-
nected to a damaged factory-built or masonry 
chimney.
For factory built, zero clearance, and ma-
sonry chimneys cleanout doors and caps 
or plugs for cleanout tee fi ttings and ash 
dumps shall be secured in place and sealed 
before installing a Direct Vent system within 
the chimney.
If the appliance shuts off during operation, 
contact a qualifi ed service person to de-
termine if a negative pressure and/or leaky 
chimney condition exists. Do not operate the 
appliance until the problem is corrected.
Approved for US Installations Only
The use of an existing chimney as an air 
intake is not covered under the ANSI Z21.88b-
1999, CSA 2.33b-M99 test methods and the 
resulting ITS/WHI product certifi cation. The 
code Authority Having Jurisdiction must be 
consulted prior to proceeding with this instal-
lation method.
Converting a Factory Built Metal 
Chimney
1)  Remove the existing chimney cap.
2)  Measure the distance from the top end of the 
chimney to the bottom of the ceiling support 
box, add 3" (76mm) to this measurement, 
and cut a section of the 4" fl ex pipe to that 
length (the fl ex should already be extended 
to its nominal length).
4)  Pass the fl ex pipe down through the center 
of the chimney system, and center the adap-
tor on the top of the chimney pipe. Drill four 
1/8" diameter holes through the adaptor and 
into the chimney top. Insure that   you are in 
fact, drilling into the metal on  the chimney. 
Twist-lock the Termination Cap (Part# 980 
or 991) onto the Adaptor. (Diagram 3 and 
4).
Diagram 1
Diagram 2
Diagram 3
5)  Pull the fl ex pipe down through the ceiling 
support box, until it protrudes approximately 
3" (76mm). Connect the fl ex pipe to the Retro 
Connector by slipping it into the 
 
4-3/4" diameter sleeve on the top side of 
the Connector. Use 3 sheet metal screws 
to assemble these two parts.
6)  Push the fl ex pipe back up into the ceiling 
support box, center the Retro Connector, and 
attach it to the support box, or decorative 
sleeve for double wall solid packed pipe, 
with the sheet metal screws (supplied). 
 
The holes in the Retro Connector are pre-
punched. Diagram 5.
Diagram 4
Diagram 5
3)  Connect the end of the fl ex pipe section to 
the underside of the Top Adaptor using 3 
sheet metal screws. Diagram 2.
7)  The connection between the appliance and 
the Retro Connector may be completed with 
sections of black direct vent pipe, together 
with an adjustable length.
INSTALLATION